background image

 

CERTIFICATE AND 

CONDITIONS OF WARRANTY

 

SECTION 1   

Q

 

15

 

6  USE OF SIGNAL RELAY 

 
An optional card is available for insertion in the slot, which is able to handle 3 isolated contact signals with which 
to remote relay UPS status information. 
 
 
The relay contacts can be 
configured NO (standard) 
or NC via jumpers on the 
optional interface card

 

 

1,2 = NC 
2,3 = NO

 

PIN LAYOUT 

 

pin 2   Mains missing 
 
pin 3   Battery almost out 
 
pin 4   General alarm 
 
pin 5   

Relay common

 

 
 
 
 
pin 6   Positive for ESD 
pin 8   Return for ESD

 

 

Logica

Gestione

Relè

R1

R2

R3

Relè

Uscite Relè

I1

Ottici

Ingresso

9 PIN

 

 
 

 

 
 
 

The maximum voltage that can be applied to the contacts is

 

60Vdc and the maximum current is 500mA.  

 

Pin DB 9 

Signals 

NC 

NO 

J

UMPERS

 

4 General 

alarm 

1-2 

2-3 

CN04 

Battery almost out 

1-2 

2-3 

CN02 

Mains down or not in limits: UPS in back-up (20 sec) 

1-2 

2-3 

CN03 

 
 

Where required, it is also possible to switch off the UPS via a remote external contact. 
The command is received by leaving the contact closed for 3 consecutive seconds. 
The external contact must be closed between pin 6 and pin 8. 
 

!

 

 
The external contact must be dedicated and at zero potential; if this condition is not 
respected, permanent damage may be caused to the UPS. 

 

 

 

Summary of Contents for ENT-RK10

Page 1: ...UPS ENTERPRISE 800 2000 VA PRODUCT MANUAL...

Page 2: ......

Page 3: ...3 2 3 Putting an external battery expansion into operation 9 4 CONFIGURATION AND START UP 10 4 1 CONFIGURATION OF THE OUTPUT VOLTAGE BATTERY EXPANSIONS 10 4 2 Power Share Configuration 2000VA version...

Page 4: ...notification of the malfunction if it is not possible to provide proof of purchase the serial number and date of production will be used to calculate expiry of the warranty which may lead to a reduct...

Page 5: ...ppropriate procedure When assembling and replacing the battery the UPS should always be switched off and disconnected from the mains power supply The UPS contains an internal power source which is the...

Page 6: ...ed via a first AC DC conversion followed by a DC AC conversion in order to provide the consumer a stable waveform that is exempt of noise or distortions and therefore completely independent of the inp...

Page 7: ...e buzzer reset alarms OFF Off button inverter OFF LED 1 Battery capacity LED bar LED 2 GREEN Mains up and regular LED 3 YELLOW Auxiliary mains present and regular bypass line LED 4 RED General alarm s...

Page 8: ...ow for adequate ventilation and access to the rear panel Make sure not to set the UPS or any other heavy object on the cables Check that the voltage and frequency preset for operation is right for you...

Page 9: ...e standards in force A distribution panel must be set up if there is not one already which can be used to isolate the mains upstream of the UPS This panel must have an automatic switch of sufficient c...

Page 10: ...ure that the safety switch on the battery expansion is in the OFF position during the connection steps Set the battery expansion unit beside the UPS on the side that does not have the air vents Connec...

Page 11: ...mode within 10 seconds In output voltage setting mode as well as the battery LED bar the no break output LED also flashes For configuration of the voltage use the same arrangements as for the battery...

Page 12: ...lication is powered by the UPS and continuous power is guaranteed If the UPS is switched on with mains absent follow the same procedure as described above and after the self test the UPS will go into...

Page 13: ...no longer be muted It is recommended to close down applications manually if the automatic shutdown procedure has not been activated via the specific software installed on the computer WARNING your ap...

Page 14: ...ation of performance 5 1 4 Switching the UPS off Partial switching off with mains present Pressing the OFF key for 2 sec in normal operation with mains present activates the partial switching off of t...

Page 15: ...ions on the leading operating systems based on JSC Java Shutdown Client Net Vision Web SNMP manager for control via LAN with TCP IP protocol and remote shutdown management the relay card with 3 zero p...

Page 16: ...ica Gestione Rel R1 R2 R3 Rel Uscite Rel I1 Ottici Ingresso 9 PIN The maximum voltage that can be applied to the contacts is 60Vdc and the maximum current is 500mA Pin DB 9 Signals NC NO JUMPERS 4 Gen...

Page 17: ...atic by pass Voltage selected 15 Overload with mains present 130 for 10 seconds AC AC efficiency 88 Crest factor 3 1 Reference normatives Standard European UPS standard EN50091 and CE marking Safety E...

Page 18: ...ted Insert the main switch Mains voltage is missing Have an electrician check the mains The MAINS LED does not come on the acoustic alarm sounds at intervals Fuse on the input faulty Replace the fuse...

Page 19: ...Q VIEW SECTION 4 800 VA 1000 VA tower front view rear view Battery extension tower 1000 VA rack 19 Battery extension rack 19 Rear view Front Rear view 4 2 1 7 5 6 8 5 6 5 7 1 4 2 5 8 5...

Page 20: ...VIEW SECTION Q 5 1500 2000 VA tower Battery extension tower rear view rear view 1500 2000 VA rack 19 Rear view Battery extension rack 19 Rear view 2 7 1 6 4 5 3 5 3 4 1 5 5 5 5 6 8 2 7 5...

Page 21: ...3 Presa di uscita power share 4 Connettore seriale RS232 USB DB9 5 Connettore batteria per espansione esterna 6 Presa di uscita per utenze 7 Presa ingresso rete e fusibile 8 Interruttore batterie 1 L...

Reviews: