54
SOCOMEC - Ref. : 875 508A
Example:
To display all the values for Diris num-
ber 5 in one inquiry, the following fra-
me should be sent:
Slave
05
Function
03
Address
High-order
07
Address
Low-order
00
Word n°
High-order
00
Word n°
Low-order
35
CRC 16
852D
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16):
Decimal Hexa.
N° of Label
Unit
address address
words
512
200
1
Network type:
0: 1BL
1: 2BL
2: 3BL
3: 3 NBL
4: 4 NBL
/
513
201
1
CT secondary:
1: 1 A
5: 5 A
A
514
202
1
CT primary
A
515
203
1
Voltage input on PT:
0: No
1: Yes
/
516
204
2
PT primary
V
518
206
1
PT secondary:
60: 60 V
100: 100 V
110: 110 V
173: 173 V
190: 190 V
V
519
207
1
Synchronisation of
I AVG/MAX:
5: 5 minutes
8: 8 minutes
10: 10 minutes
15: 15 minutes
20: 20 minutes
30: 30 minutes
60: 60 minutes
/
520
208
1
Synchronisation of
P/Q/S AVG/MAX:
5: 5 minutes
8: 8 minutes
10: 10 minutes
15: 15 minutes
20: 20 minutes
30: 30 minutes
60: 60 minutes
/
521
209
1
OUT 1 allocation
0: kWh +
1: kvarh +
2: kVA
3: kWh –
4: kvarh -
/
522
20A
1
OUT1 pulse value:
0: 0.1 kWh/kvarh/kVA
1: 1 kWh/kvarh/kVA
2: 10 kWh/kvarh/kVA
3: 100 kWh/kvarh/kVA
4: 1000 kWh/kvarh/kVA
5: 10000 kWh/kvarh/kVA
/