52
SOCOMEC - Ref. : 875 508A
Example:
To display all the values for Diris num-
ber 5 in one inquiry, the following fra-
me should be sent
Slave
05
Function
03
High-order
address
03
Low-order
address
00
High-order
word n°
00
Low-order
word n°
62
CRC 16
C5E3
Zone size: 98 words (decimal) or 62 (hexadecimal).
Decimal Hexa.
Number
Text
Unit
address address of words
820
334
2
Power factor phase 3
-: capacitive and +: inductive
0,001
822
336
2
Average values I1
mA
824
338
2
Average values I2
mA
826
33A
2
Average values I3
mA
828
33C
2
Average value
∑
Active power +
kW/100
830
33E
2
Average value
∑
Active power -
kW/100
832
340
2
Average value
∑
Reactive power +
kvar/100
834
342
2
Average value
∑
Reactive power -
kvar/100
836
344
2
Average value
∑
Apparent power
kVA/100
838
346
2
Maximum value I1
mA
840
348
2
Maximum value I2
mA
842
34A
2
Maximum value I3
mA
844
34C
2
Maximum value
∑
Active power +
kW/100
846
34E
2
Maximum value
∑
Active power -
kW/100
848
350
2
Maximum value
∑
Reactive power +
kvar/100
850
352
2
Maximum value
∑
Reactive power -
kvar/100
852
354
2
Maximum value
∑
Apparent power
kVA/100
854
356
2
Hour meter
1/100 h
856
358
2
Active
kWh
858
35A
2
Reactive
kWh
860
35C
2
Apparent energy
kVAr
862
35E
2
Active energy -
kWh
864
360
2
Reactive energy -
kvarh