COMPLIANCE
european emc Directive no. 2004/108/ec (15/12/2004)
lv Directive no. 2006/95/ec Dated 12 December 2006
iec 62053-21 / iec 62052-11
SYSTEM CONNECTION
Supply types / number of wires
Single phase 2 wires 230v
three phase 3 wires 3x230v / 3x400v and three phase 4 wires
3x230/400v
management
Detection of cabling error
frequency
50 and 60 Hz (± 5 Hz)
SUPPLY
autosupplied
CONSUMPTION
Supply
< 10 va or 2 w
current circuit
< 2.5 va
CURRENT (TRMS)
Starting current (ist)
80 ma
minimum current (imin)
0.5 a
transition current (itr)
2 a
reference current (iref)
20 a
Permanent overload (imax)
100 a
Short-term over-current
3000 a for 10 ms (en50470-3 and iec 62053-21)
VOLTAGE (TRMS)
Direct measurement
230vac Phase/neutral 400v ac Phase/Phase ± 15%
Permanent overload
230 / 400 v ac + 15%
POWERS
active
Yes
reactive no*
resolution
0.1 kw
ENERGY
active
Yes
reactive no*
total and partial metering
Yes (0 to 999999.9 kwh)
Bidirectional metering (ea+ and ea-)
Yes
resolution
1 kwh
interval
---
load curve
---
integration time for load curves
---
ACCURACY
active energy
class 1 (iec 62053-21)
TARIFFS
tariff management
no*
number of tariffs managed
4*
tariff exchange input
no*
METROLOGICAL LED
impulse weight
500 impulses / kwh or 2wh / impulse
colour red
DISPLAY
type
7 Digit leD with blue back-lighting
refresh time
1s
Back-lighting illumination time
30 s
list of functions displayed
cf. table below.
* functions available only via communication, the complete list of these functions is given in the down-
loadable JBUS/moDUS communication table.
41
COUNTIS E33
GB