Mounting instructions for butterfly valves 

SYLAX DN 25-350 

6

Before putting valve into operation, check that: 
 

- The working conditions are compatible with the details given on the identification plate , this instruction notice and the 

 

   manufacturer

s details (technical data sheet, price list catalogue, advisory service). 

 

- The indicator on the control or the handle position (disc direction), properly indicates the position of the disc. 

 

- All the connections have been properly made (pneumatic, electrical, hydraulic). 

 

- The valve works effectively when tried (check several times). If necessary certain adjustments may be made to the end stops by 

         qualified personnel. 

 

 

On a new installation or after maintenance, the circuit must be rinsed with the valve completely open in order to remove solid matter 
which may damage the internal parts of the valve. 

 

 

During a prolonged stoppage, a change in the state of the fluid may result in damage when the installation is brought back into service 
(solidification….). Establish an adequate procedure programme for cleaning the system.  

Maintenance 

Maintenance and repair work must be carried out by qualified personnel. 
During opening, closing and testing of the valve, take care not to put hands or any other object in the area of the disc. 

Manipulate the liner and the disc with gloves in order to avoid damaging them by scratches. 
 

 

Removing the valve from the installation

 

  The pipe must be depressurized and purged (emptied of its fluid) in order to avoid any danger to the operator. If the installation has 

   carried  fluids which are dangerous in themselves if in contact with the outside atmosphere (inflammable, corrosive, toxic, 
   explosive..) it must be thoroughly cleaned to eliminate all risks. 

   All fluid remaining in the valve must be removed. 
   The temperature of the valve must be lower than 35°C to avoid all risk of burning. 

    If necessary, perform the operation using suitable protection (clothing, gloves, mask…). 

Warning 

: when used in an ATEX zone, electrostatic charges may be present inside the valve (disc, liner). These electrostatic charges 

       created by the flow of the fluid may present a risk of explosion. The user is responsible for taking all precautions to avoid this risk. 
                Place the disc at 10° from opening before removing the valve. 

 
Where a control uses an external energy source, it is essential to isolate this source before any operation. 

 

 Dismantling the control from the valve.

 

    Check the mounting position of the control before dismantling. 
    To reassemble, use all the original screws etc. 

 

 

Maintenance of the valve

 

    All spare parts must be genuine Socla. 
    All spare parts must be used. 

    The use of grease is not allowed in a silicon free environment. 
    Greases  and silicones used must be compatible with the fluid being carried and the installation constraints. 

 

Use 

In order to guarantee the good working of the valve, we advise to  carry out 1 actuation minimum per month (full opening  
and closing). 

In ATEX zone, valve and actuation must be cleaned regularly in order to avoid any accumulation of dusts. 
The hot or cold parts of valve and actuation presenting a danger for the operator must be protected. 

Do not insert fingers close to parts which are moving or between the lever and the handle during its operation. 
In ATEX zone, the end of line mounting is not authorized. 

Modifications, errors and printing mistakes cannot be held responsible for damages incurred. Socla reserves 
the right to  modify  products without prior warning. All trademarks of these products are the property of the 
respective companies . 

Summary of Contents for SYLAX DN 100

Page 1: ...inns tillg ngligt p v r internet sida i alla officiella spr k inom EU p efterfr gen fr n v rt f rs ljningsavdelning Cette Notice d Instruction est disponible dans les langues officielles de la Communa...

Page 2: ...nt internal shocks generated by granular substances shock waves present in the installation water hammer or risks from foreign objects which may be present in the installation Classification of the va...

Page 3: ...allows its use in a determined area use in another area is under the responsibility of the user An identification plate with information required by the Directives is attached to the valve This plate...

Page 4: ...ns Follow the general procedure of installation with mounting the valve and its actuator in normally closed position NC Uncouple the valve and its actuator by unscrewing the four nuts 4 and with takin...

Page 5: ...langes while removing the flange retractors and tightening the nuts by hand 6 Close the valve carefully making sure that the butterfly turns freely 7 In ATEX zone category 2 connect the earth strap to...

Page 6: ...the procedure installation on existing pipe work from point 3 Flange ratings The Sylax butterfly valves DN 25 350 has been designed to be fitted between standard flanges Only flanges type 11 21 and 3...

Page 7: ...it must be thoroughly cleaned to eliminate all risks All fluid remaining in the valve must be removed The temperature of the valve must be lower than 35 C to avoid all risk of burning If necessary pe...

Page 8: ...an ohmmeter test according to EN 1226 2 annex B point b 2 2 2 and B 2 3 1 In ATEX zone this test is compulsory Fit the valve to the pipe work see installation paragraph Guide bushes It is recommended...

Page 9: ...on a periodic basis under normal conditions It is the responsibility of the user to check after the installation of the valve that there is no leakage Especially in case of deliberate internal explos...

Reviews: