Socla SYLAX DN 100 Mounting Instructions Download Page 6

  

 Installation on new pipe work

 

1. 

Make sure that: 

 

- The flange surfaces are clean and undamaged. 

 

- The valve fits between the flanges without difficulty and without damaging the sleeve. Prise apart the flanges with suitable tools 

         without damaging the flanges. 
 

- The internal diameter of the flanges conforms to the dimensions in the «

 

flange ratings

 

» table. 

 

- Nothing interferes with the movement of the shutter when the valve is operating. 

2. 

Close the disc so that it is about 5 to 10mm inside the casing. 

3. 

Fit the two flanges to the casing using some bolts, tighten the valve a little between the two flanges.  

4.

 Fix this whole assembly to the pipe work. 

5. 

Consolidate the flanges to the pipe work by welding at several points. 

6. 

Unscrew the bolts and remove the valve from between the flanges. 

 

Never weld the flanges with the valve in place : risk of burning the elastomer liner. 

7.

 Finish welding the flanges and allow to cool completely. 

8. 

Return the valve to the pipe work using the procedure "installation on existing pipe work".(from point 3.). 

 

 Flange ratings : 

The Sylax butterfly valves DN 25-350 has been designed to be fitted between standard flanges. Only flanges type 11, 21 and 34 
according to EN 1092-1 are completely suitable for this valve. 

For other flange models, please check the figures in the table below. Non appropriate connections will cancel our guarantee. 

 
 

 
 

 
 

 
 

 
 

 
 

 

 

 Installation conditions

 

It is recommended that the distances indicated below be respected in order to prolong the life of the valve. Mounting the valve close to 
pipe work junctions places it in turbulent zones and increases wear. 

Mounting instructions for butterfly valves 

SYLAX DN 25-350 

5

DN 

Ø A0 

Ø A1 mini 

Ø A2 maxi 

Ø B mini 

25 

32 

44 

60 

32/40 

43 

33 

51 

80 

50 

54 

40 

60 

90 

65 

70 

59 

74 

110 

80 

85 

78 

91 

128 

100 

100 

97 

108 

148 

125 

125 

119 

143 

178 

150 

150 

146 

166 

202 

200 

200 

196 

224 

258 

250 

250 

246 

280 

312 

300 

300 

296 

329 

365 

350 

340 

335 

369 

415 

Modifications, errors and printing mistakes cannot be held responsible for damages incurred. Socla reserves 
the right to  modify  products without prior warning. All trademarks of these products are the property of the 
respective companies . 

Summary of Contents for SYLAX DN 100

Page 1: ...inns tillg ngligt p v r internet sida i alla officiella spr k inom EU p efterfr gen fr n v rt f rs ljningsavdelning Cette Notice d Instruction est disponible dans les langues officielles de la Communa...

Page 2: ...nt internal shocks generated by granular substances shock waves present in the installation water hammer or risks from foreign objects which may be present in the installation Classification of the va...

Page 3: ...allows its use in a determined area use in another area is under the responsibility of the user An identification plate with information required by the Directives is attached to the valve This plate...

Page 4: ...ns Follow the general procedure of installation with mounting the valve and its actuator in normally closed position NC Uncouple the valve and its actuator by unscrewing the four nuts 4 and with takin...

Page 5: ...langes while removing the flange retractors and tightening the nuts by hand 6 Close the valve carefully making sure that the butterfly turns freely 7 In ATEX zone category 2 connect the earth strap to...

Page 6: ...the procedure installation on existing pipe work from point 3 Flange ratings The Sylax butterfly valves DN 25 350 has been designed to be fitted between standard flanges Only flanges type 11 21 and 3...

Page 7: ...it must be thoroughly cleaned to eliminate all risks All fluid remaining in the valve must be removed The temperature of the valve must be lower than 35 C to avoid all risk of burning If necessary pe...

Page 8: ...an ohmmeter test according to EN 1226 2 annex B point b 2 2 2 and B 2 3 1 In ATEX zone this test is compulsory Fit the valve to the pipe work see installation paragraph Guide bushes It is recommended...

Page 9: ...on a periodic basis under normal conditions It is the responsibility of the user to check after the installation of the valve that there is no leakage Especially in case of deliberate internal explos...

Reviews: