SMS ControlMate/3G © 2016-2018
Page 26 of 56
POWER & CONTROL CONNECTIONS
REAR connection points on the ControlMate module
The rear of the controller module contains
–
The modem and SIM card
holder. Under the edge of the modem, there is a RED power LED,
and a BLUE network LED… these are control
led by the software.
The
cellular antenna
may be attached directly to the modem, or an external antenna with a
longer cable may be fitted in low-signal areas.
The
DC power supply
input (nominally 12-15 volts DC polarity protected)
2-way 5.08mm
Using
24V
directly into the ControlMate requires a voltage regulator
(supplied free upon request). Where possible, use a clean 12-15V source,
or an external regulator to reduce the 24V source down to 12-15VDC
This 24V regulator is available to drop local 24V down to 12-15V for the controller
A 6-pin header is provided
for factory use only
- do not connect to this point.
The
soft-restart button
. This does not affect the controller hardware reset pin, which is only
available on the console connector (below).
Holding this button for 5-seconds during power-on/reset will CLEAR ALL USER CONFIGURATION SETTINGS to
default values. The LCD and console session will display warnings if a clear-all is about to take place.
Under a ‘normal’ soft
-restart EEPROM values (counters, output states etc.) are saved before all power-fail, or soft
restart events. Soft-restart only functions whe
n the controller is ‘running’.
((
Only
a hardware reset will reset the unit
without
saving the current volatile states, counter. They will return to
their most recently saved value at the next power-on cycle. ))
You can also see the green
‘
activity
’
LED,
and red ‘attentio
n
’
indicators
.
A
‘
console’
connector
for use with a PC or terminal via USB or serial
connection. TTL levels @ 115200-8-N-1
Pins:
1=0V / 2=
RxD
/ 3=TxD
→
/ 4=DTR/
Reset / 5=+5V
→
@ max 200mA
A 10-way IDC ribbon-header for the
LCD and LED ribbon cable
.
Summary of Contents for ControlMate
Page 2: ...SMS ControlMate 3G 2016 2018 info SL4P net Page 2 of 56 BLANK PAGE...
Page 6: ...SMS ControlMate 3G 2016 2018 info SL4P net Page 6 of 56 BLANK PAGE...
Page 9: ...SMS ControlMate 3G 2016 2018 info SL4P net Page 9 of 56 CONTROLMATE V2 LOGICAL BLOCK DIAGRAM...
Page 10: ...SMS ControlMate 3G 2016 2018 info SL4P net Page 10 of 56 BLANK PAGE...
Page 52: ...SMS ControlMate 3G 2016 2019 info SL4P net Page 52 of 56 BLANK PAGE...
Page 54: ...SMS ControlMate 3G 2016 2019 info SL4P net Page 54 of 56 BLANK PAGE...
Page 56: ...SMS ControlMate 3G 2016 2019 info SL4P net Page 56 of 56 BACK COVER...