HEX390 Installation & Commissioning Instructions September 2016

7

HEX

Drain 

adaptor

P trap in condensate 

drain hose

Drain Adaptor

Bottom of unit

Drain installation

Securely attach the provided drain adaptor 

(located inside HEX filter cover) to the bottom of 

HEX unit.  HEX unit must be level. Run the drain 
tubing from the adaptor to outside with a “P trap”, 
as illustrated.

Fresh Air and Exhaust Grille

Install underneath the soffit with a minimum 6m 

separation between the exhaust and fresh air 
grille to prevent cross contamination. Use the 

nude and acoustic ducting (Silentflex) from the 

fresh air and exhaust grilles respectively to the 
unit. If access is limited, please consider using 
through roof cowls, such as the MAD204T.

 

Return Grilles  

Mount the provided return air grilles as suits the 
homeowner, one in the heat source room and one 
in the hallway central to the supply grilles.  Use 
the Insulated ducting from the grille to the unit. 

Exhaust Air

Return Air filter

HEX body

Supply Air

Return Air

Outside Air

Fresh Air filter

Filters

The unit is supplied with two G3 pre filters. If 
required, an F7 filter (FBPF7) can be 
installed in the supply side for extra filtration. 
Alternatively a standard EU2 filter can be used 

(FBPF2).

Supply Grilles  

Mount the provided supply air grilles as suits the 
homeowner, bedrooms and living areas, with a 

maximum of five outlets for optimum performance. 

Use the acoustic ducting. It is recommended that 
the supply outlet be between these grilles and the 
unit. 

Cleaning the filters

The internal filters are designed as secondary 
filters (there should be extended surface filters 

cleaning the air before reaching the unit).  

However, when unit filters are heavily soiled, 
wash or replace the filter material with "

HexFilter

(234x380mm) or "

HexFilter 222

" (222x380mm) for 

2015 and earlier models.  
To wash: use vacuum cleaner to remove excess 
dust, then wash in warm detergent treated water, 

keep filters flat or leave in frame to wash. 

Summary of Contents for HEX390 Series

Page 1: ...er 2016 1 HEX390 Domestic Ventilation System with Heat Exchanger Balanced Pressure Ventilation Installation Commissioning Instructions for Digital or Manual controller HEX390 Supply Air Return Air Exhaust Air Outside Air HEX390 Heat Exchange unit v3 1 762 ...

Page 2: ...______________________________________________________________ HEX390 Warranty 5 years manufacturing warranty from date of first retail purchase This HEX product when delivered to you in new condition from a HEX authorized dealer and used in normal conditions will be free from any defects in manufacturing materials and workmanship for the periods set out above Warranty Period Any faulty goods will...

Page 3: ... with inadequate kitchen extraction or with smokey log burners we recommend a pre filter see over page 13 In colder areas an auxiliary inline duct heater is recommended see over page Pre checks Recommendations 1 Before installation ensure the system suits your requirements 2 Check that adequate heat sources are present for the optimum performance of the system 3 Make sure that enough space is avai...

Page 4: ...Fuse 10A Ceramic Slow Blow Diffusers cut out size Cut out size Lounge supply 200mm Swirl Diffuser 222mm Bedrooms supply 150mm Cone Diffuser 180mm Return 200mm Circular Egg Crate 262mm Fresh air Exhaust 200mm Square Louvre Optional Extras Item Code F7 Filter FBPF7 Filter Box for F7 filter FBP200 Additional 150mm supply HEXext150supply Additional 200mm supply HEXext200supply Additional Extract HEXex...

Page 5: ...1 1 150mm circular cone diffuser 3 2 1 200mm x 6m Silentflex 1 1 200mm x 3m Silentflex 2 2 1 150mm x 3m Silentflex 3 2 1 200 200 200 Y connection 1 1 1 200 150 150 y connection 1 150 150 150 Y connection 1 200 150 150 150 Branch 1 Extract 200mm Egg crate circular grille 2 1 1 200mm x 6m insulated duct 1 200mm x 3m insulated duct 3 1 200 200 200 Y joint 1 1 Fresh 200mm square Louvre Grille 1 1 200m...

Page 6: ...silent 150mm x 3m silent 150mm x 3m silent 200mm x 3m silent 200mm x 3m insulated Drain 200mm x 6m nude 6m 200mm x 6m silent 200mm louvre sq grille 200mm louvre sq grille 150mm Cone Diffuser 200mm Swirl Diffuser 150mm Cone Diffuser 150mm Cone Diffuser 200mm Circular Eggcrate General Layout Up to 6 times faster to install than traditional methods Keyless no tool required for adjustment Ergonomic bu...

Page 7: ...es Use the Insulated ducting from the grille to the unit Exhaust Air Return Air filter HEX body Supply Air Return Air Outside Air Fresh Air filter Filters The unit is supplied with two G3 pre filters If required an F7 filter FBP200 FBPF7 can be installed in the supply side for extra filtration Alternatively a standard EU2 filter can be used FBP200 FBPF2 Supply Grilles Mount the provided supply air...

Page 8: ...adjacent to one of the extract grilles Temperature sensor mounted in fresh air inlet Temperature sensor wire plugs in here Cat5 cable to digital wall controller For digital controller mount with pack glands downwards In line Duct Heater for digital model only If installing HT or HT15 ensure the duct heater is securely installed horizontally and ensure the air flow meets the minimum required Digita...

Page 9: ...set to 30 the unit will turn off if the incoming fresh air is above 30ºC Return Air filter Fresh Air filter Optional Internal On Off Thermostat Electrical Supply 230VAC by installer Electrical supply must be installed by a registered electrician as per the schematics on pages 10 11 Heater Connection Return Air Shielded don t cut Cables The 5 core cable fan loom goes to the attic box for both manua...

Page 10: ...HEX390 Installation Commissioning Instructions September 2016 10 Wiring schematic Manual 3speed switch The attic box also comes with a two core wire for use with the optional thermostat ...

Page 11: ...ic damper kit 1 2 3 P N P1 N P3 N NC C 240VAC MOTOR HEAT Vent Circuit Board Patch lead socket Isolator Switch NO Heat Sensor Plug Grey HT15D Only Green Blue Brown Grey Mode Fan Diverting Branch Motor Heater 1 2 3 N P P N If damper operates in reverse change CW CCW switch on motor body to correct Diverting branch motor Hall controller For heated units only Heat sensor For attic damper kit ensure th...

Page 12: ...s not affect operation if a damper is not installed Symptoms Solutions Fans not operational Check circuit breaker in the mains switch board Check power to the hall controller If hall controller is active check the 2A fuse in the attic controller after isolating the power to the unit Fan too noisy Check the Max Fan Speed setting match the recommended setting for the house size lower the speed of fa...

Page 13: ...Press button to toggle between Yes No or other options then press Mode to advance through the menu Once a setting is changed on the menu it is automatically registered Hold down the Mode key to accelerate through the menu Options are on following pages Please note if settings are changed from recommendations performance of the unit may be reduced Display Key Δ Outside Air Temperature Inside Air Te...

Page 14: ... a max of 100 House size Max Setting Upto 120m2 50 120m2 180 m2 70 180 m2 250 m2 100 280 Two or more units recommended 3 Fan Speed Heat default 45 Range is 30 to 60 adjustable in 1 increments using up down arrows Fan Speed Heat sets a minimum speed for the fan to ensure enough airflow for the heater to operate There are many duct fan combinations some more restrictive to airflow than others Theref...

Page 15: ... Degree Offset default 0 C As above 10 Heat P band default 5 C Range 1 7 C Heat Proportional Band When heater is fitted and conditions call for its operation heater will start heating at 20 when OS outside drops to reference temp default 12 C and will operate at 100 when temperature has dropped by a further default 5 C ie when OS is 7 C 11 Summer Temp S down default 27 C Range 25 35 C When OS outs...

Page 16: ...e cleaned replaced Clock function has battery back up in the event of a power failure Time can be set adjusted by pressing mode and buttons together until Entering Menus then Set Clock appears Time can then be adjusted using up down buttons once correct time is set press mode to save new setting Optional Attic Damper Kit A diverting branch can be attached to divert the intake from the outside air ...

Reviews: