HEX390 Installation & Commissioning Instructions September 2016

14

1. 

Heater Kit 

Yes/No (default Yes)

If No - heater options are removed from all menus. 
If Yes - heater options are available in User menu - Heater On/Off for continuous or night 
heat (to times as set below) .   

 

 

 

To set night heat option:

• 

press        up arrow to select Yes, then:

• 

press        mode to display 

‘Heater Times’

>display then changes automatically to show 

the current settings (default:                        ) >display changes again to 

‘Change Times’ 

Yes/No (default No).  

• 

At this point, use        then          to select Yes & change the times.

• 

Select desired  

Heater ON

    time in Hours:Mins using         or

• 

Select desired  

Heater OFF

   time in Hours:Mins using         or 

• 

Heater Test Yes/No (default No)

• 

change to Y, heater test will be performed.  If there are any faults (including no 
heater connected), 

‘Heater Fault’

 will display.  (See menu item 3.Fan Speed Heat for 

possible Heater Fault causes.) To reset Heater Fault display, turn unit off.

2. 

Max Fan Speed 

(default 60%) – Range is 35% to 100% adjustable in 1% increments using up 

& down arrows.  For a large house set to a max of 100%.

House size

Max Setting

Upto 120m2

50%

120m2 - 180 m2

70%

180 m2-250 m2

100%

280 +

Two or more units recommended

3. 

Fan Speed Heat

 (default 45%) – Range is 30% to 60% adjustable in 1% increments using up & 

down arrows.

Fan Speed Heat

 sets a minimum speed for the fan to ensure enough airflow for the heater 

to operate.  There are many duct fan combinations, some more restrictive to airflow than 

others.  Therefore, when setting up, the installer must check that the heater operates 
without 

‘Heater Fault’

 flashing on the display.   

‘Heater Fault’

 is triggered when the heater 

is operating but draws no current, this is most often due to insufficient airflow causing 
the airflow proving switch to cut off. If there is insufficient airflow, increase the ‘Fan Speed 

Heat’ setting. Heater fault may also be caused by manual reset thermal cutouts which may 
need to be reset.

4. 

Winter Mode

 Yes/No (default Yes). Winter mode shuts the system down when the outside air 

temperature gets below eg 2°C.  If Winter Mode is on, another menu item will appear to allow 
adjustment of actual shut down temp: Range -2°C to +5°C.

Heater ON 19:00

Heater OFF07:00

Digital Controller - Commissioning Instructions - Menu Options

Digital Controller - Commissioning Instructions 

(continued)

Summary of Contents for HEX390 Series

Page 1: ...er 2016 1 HEX390 Domestic Ventilation System with Heat Exchanger Balanced Pressure Ventilation Installation Commissioning Instructions for Digital or Manual controller HEX390 Supply Air Return Air Exhaust Air Outside Air HEX390 Heat Exchange unit v3 1 762 ...

Page 2: ...______________________________________________________________ HEX390 Warranty 5 years manufacturing warranty from date of first retail purchase This HEX product when delivered to you in new condition from a HEX authorized dealer and used in normal conditions will be free from any defects in manufacturing materials and workmanship for the periods set out above Warranty Period Any faulty goods will...

Page 3: ... with inadequate kitchen extraction or with smokey log burners we recommend a pre filter see over page 13 In colder areas an auxiliary inline duct heater is recommended see over page Pre checks Recommendations 1 Before installation ensure the system suits your requirements 2 Check that adequate heat sources are present for the optimum performance of the system 3 Make sure that enough space is avai...

Page 4: ...Fuse 10A Ceramic Slow Blow Diffusers cut out size Cut out size Lounge supply 200mm Swirl Diffuser 222mm Bedrooms supply 150mm Cone Diffuser 180mm Return 200mm Circular Egg Crate 262mm Fresh air Exhaust 200mm Square Louvre Optional Extras Item Code F7 Filter FBPF7 Filter Box for F7 filter FBP200 Additional 150mm supply HEXext150supply Additional 200mm supply HEXext200supply Additional Extract HEXex...

Page 5: ...1 1 150mm circular cone diffuser 3 2 1 200mm x 6m Silentflex 1 1 200mm x 3m Silentflex 2 2 1 150mm x 3m Silentflex 3 2 1 200 200 200 Y connection 1 1 1 200 150 150 y connection 1 150 150 150 Y connection 1 200 150 150 150 Branch 1 Extract 200mm Egg crate circular grille 2 1 1 200mm x 6m insulated duct 1 200mm x 3m insulated duct 3 1 200 200 200 Y joint 1 1 Fresh 200mm square Louvre Grille 1 1 200m...

Page 6: ...silent 150mm x 3m silent 150mm x 3m silent 200mm x 3m silent 200mm x 3m insulated Drain 200mm x 6m nude 6m 200mm x 6m silent 200mm louvre sq grille 200mm louvre sq grille 150mm Cone Diffuser 200mm Swirl Diffuser 150mm Cone Diffuser 150mm Cone Diffuser 200mm Circular Eggcrate General Layout Up to 6 times faster to install than traditional methods Keyless no tool required for adjustment Ergonomic bu...

Page 7: ...es Use the Insulated ducting from the grille to the unit Exhaust Air Return Air filter HEX body Supply Air Return Air Outside Air Fresh Air filter Filters The unit is supplied with two G3 pre filters If required an F7 filter FBP200 FBPF7 can be installed in the supply side for extra filtration Alternatively a standard EU2 filter can be used FBP200 FBPF2 Supply Grilles Mount the provided supply air...

Page 8: ...adjacent to one of the extract grilles Temperature sensor mounted in fresh air inlet Temperature sensor wire plugs in here Cat5 cable to digital wall controller For digital controller mount with pack glands downwards In line Duct Heater for digital model only If installing HT or HT15 ensure the duct heater is securely installed horizontally and ensure the air flow meets the minimum required Digita...

Page 9: ...set to 30 the unit will turn off if the incoming fresh air is above 30ºC Return Air filter Fresh Air filter Optional Internal On Off Thermostat Electrical Supply 230VAC by installer Electrical supply must be installed by a registered electrician as per the schematics on pages 10 11 Heater Connection Return Air Shielded don t cut Cables The 5 core cable fan loom goes to the attic box for both manua...

Page 10: ...HEX390 Installation Commissioning Instructions September 2016 10 Wiring schematic Manual 3speed switch The attic box also comes with a two core wire for use with the optional thermostat ...

Page 11: ...ic damper kit 1 2 3 P N P1 N P3 N NC C 240VAC MOTOR HEAT Vent Circuit Board Patch lead socket Isolator Switch NO Heat Sensor Plug Grey HT15D Only Green Blue Brown Grey Mode Fan Diverting Branch Motor Heater 1 2 3 N P P N If damper operates in reverse change CW CCW switch on motor body to correct Diverting branch motor Hall controller For heated units only Heat sensor For attic damper kit ensure th...

Page 12: ...s not affect operation if a damper is not installed Symptoms Solutions Fans not operational Check circuit breaker in the mains switch board Check power to the hall controller If hall controller is active check the 2A fuse in the attic controller after isolating the power to the unit Fan too noisy Check the Max Fan Speed setting match the recommended setting for the house size lower the speed of fa...

Page 13: ...Press button to toggle between Yes No or other options then press Mode to advance through the menu Once a setting is changed on the menu it is automatically registered Hold down the Mode key to accelerate through the menu Options are on following pages Please note if settings are changed from recommendations performance of the unit may be reduced Display Key Δ Outside Air Temperature Inside Air Te...

Page 14: ... a max of 100 House size Max Setting Upto 120m2 50 120m2 180 m2 70 180 m2 250 m2 100 280 Two or more units recommended 3 Fan Speed Heat default 45 Range is 30 to 60 adjustable in 1 increments using up down arrows Fan Speed Heat sets a minimum speed for the fan to ensure enough airflow for the heater to operate There are many duct fan combinations some more restrictive to airflow than others Theref...

Page 15: ... Degree Offset default 0 C As above 10 Heat P band default 5 C Range 1 7 C Heat Proportional Band When heater is fitted and conditions call for its operation heater will start heating at 20 when OS outside drops to reference temp default 12 C and will operate at 100 when temperature has dropped by a further default 5 C ie when OS is 7 C 11 Summer Temp S down default 27 C Range 25 35 C When OS outs...

Page 16: ...e cleaned replaced Clock function has battery back up in the event of a power failure Time can be set adjusted by pressing mode and buttons together until Entering Menus then Set Clock appears Time can then be adjusted using up down buttons once correct time is set press mode to save new setting Optional Attic Damper Kit A diverting branch can be attached to divert the intake from the outside air ...

Reviews: