Installation
30
General information
This appliance is suitable for installation with
Natural Gas or ULPG (propane/butane).
Refer to “If the gas leak persists, contact the
nearest supplier.” for the relevant burner
pressure and appropriate injector sizes.
When the appliance is to be connected to
Natural Gas then the pressure regulator
supplied must be fitted to the gas inlet. A test
point (for checking the gas pressure) is
supplied either with the regulator or as a
separate fitting in the case of ULPG
(propane) appliances.
This appliance must be installed by an
authorised person in accordance with this
instruction manual, AS/NZS 5601.1 –
Gas installations (installation and pipe
sizing), local gas fitting regulations, local
electrical regulations, local water
regulations, Building Code of Australia and
any other government authority.
LPG:
the supplied hose and regulator must
be fitted to the appliance inlet connection.
Gas pressure is 2.75 kPa, the appliance
test point is located on the regulator.
Natural Gas:
the supplied regulator must
be fitted to the appliance inlet connection.
Gas pressure must be adjusted to 1.0 kPa
when approximately 50% of the burners are
on high flame; the appliance test point is
located on the regulator. This appliance is
suitable for connection with rigid pipe or
flexible hose. The isolating manual shut-off
valve connection point must be accessible
when the appliance is installed.
Connecting the gas cylinder to the
appliance
Connection of the appliance to the gas
supply must be performed in accordance
with the requirements of AS5601/ AG601.
This product is designed for use only with
LPG gas in suitable cylinders obtainable
from specialised shops. The appliance
comes complete with a rubber hose with
pressure regulator and unions. The pressure
regulator is preset in the factory to ensure
the appliance functions to the highest
standards. The diagram below shows how
to connect the hose supplied to the product
and the gas cylinder.
The operation of the appliance
must be tested by the installer to
confirm all burner flames are blue
in colour, stable and completely
ignite at both high and low flame
settings with no appreciable
yellow tipping, carbon deposition,
lifting, floating, lighting back or
objectionable odour. Test burners
individually and in combination.
Minimum LPG cylinder is 4.5 kg
and the maximum LPG cylinder il
9.0 kg.