Design / Selection

 

 
 

3. Surge voltage suppressor 

1) The surge voltage suppressor built into the valve is intended to 

protect the output contacts so that the surge generated inside 
valve does not adversely affect the output contacts. Therefore, if 
an overvoltage or overcurrent is received from an external 
peripheral device, the surge voltage protection element inside 
the valve is overloaded, causing the element to break. In the 
worst case, the breakage causes the electric circuit to enter 
short-circuit tatus. If energizing continues while in this state, a 
large current flows. This may cause secondary damage to the 
output circuit, external peripheral device, or valve, and may also 
cause a fire. So, take appropriate protective measures, such as 
the installation of an overcurrent protection circuit in the power 
supply or a drive circuit to maintain a sufficient level of safety. 

2) If a surge protection circuit contains nonstandard diodes, such 

as Zener diodes or varistor, a residual voltage that is in 
proportion to the protective circuit and the rated voltage will 
remain. Therefore, take into consideration the surge voltage 
protection of the controller. In the case of diodes, the residual 
voltage is approximately 1V. 

 

4. Surge voltage intrusion 

With non-polar type solenoid valves, at times of sudden 

interruption of the loading power supply, such as emergency 

shutdown, surge voltage intrusion may be generated from loading 

equipment with a large capacity (power consumption), and a 

solenoid valve in a de-energized state may switch over (see 

Figure 1). 

When installing a breaker circuit for the loading power supply, 

consider using a solenoid valve with polarity (with polarity 

protection diode), or install a surge absorption diode between the 

loading equipment COM line and the output equipment COM line 

(see Figure 2). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

5. 

Operation in a low temperature condition 

It is possible to operate a valve in extreme temperature, as low 
as -10

o

C

Take appropriate measures to avoid freezing of 

drainage, moisture etc. in low temperature. 

6. 

Operation for air blowing

 

When using a solenoid valve for air blowing, use an external 
pilot type. 
Use caution because the pressure drop caused by the air 
blowing can have an affect on the internal pilot type valve when 
internal pilot type valves and external pilot type valves are used 
on the same manifold. 
Additionally, when compressed air within the pressure range of 
the established specifications is supplied to the external pilot 
type valve’s port, and a double solenoid valve is used for air 
blowing, the solenoids should normally be energized when air is 
being blown. 

7. Mounting orientation 

Mounting orientation is free. 

8.

 

Initial lubrication of main valve 

The following initial lubricant has already been applied to the 

main valve. 

• Rubber seal, spool valve: Grease 

Please consult with SMC, as there are some standard valve 

products that use fluorine grease for food processing equipment 

(NSF H-1). 

9. For the pilot EXH (PE) port 

If the solenoid valve and the manifold’s pilot EXH (PE) port is 
restricted extremely or blocked, abnormal operation of the 
solenoid valve may occur. 

SX3000/5000/7000  Series   

Precautions for 5  Port Solenoid Valve  2 

 

 

Be sure to read before handling.

 

 

Caution 

 

 

- 5 - 

 

SX3000-OMM0002-B 

 

Summary of Contents for SX3000 Series

Page 1: ...Doc no SX3000 OMM0002 B PRODUCT NAME 5 Port Solenoid Valve MODEL Series Product Number SX3000 5000 7000 Series...

Page 2: ...Precautions on Design Selection 4 5 Mounting 6 Piping 6 Wiring 6 Lubrication 7 Air Supply 7 Operating Environment 7 Maintenance 8 Specific Product Precautions 9 to 11 Valve Construction 12 13 Troubles...

Page 3: ...e when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly oper...

Page 4: ...duct 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from this 1 year...

Page 5: ...e In addition at the time of vacuum adsorption be sure to vacuum at all times Failure to do so may result in foreign matter sticking to the adsorption pad or air leakage causing the workpiece to drop...

Page 6: ...d state may switch over see Figure 1 When installing a breaker circuit for the loading power supply consider using a solenoid valve with polarity with polarity protection diode or install a surge abso...

Page 7: ...itable wrench to tighten the hexagonal portion of the body an additional 1 6 to 1 4 turn The reference value for the tightening torque is 1 to 1 5 N m Note Excessive tightening may damage the thread p...

Page 8: ...ll an air filter Install an air filter upstream near the valve Select an air filter with a filtration size of 5 or smaller 3 Take measures to ensure air quality such as by installing an aftercooler ai...

Page 9: ...o operate 3 Low frequency operation Valves should be operated at least once every 30 days to prevent malfunction Use caution regarding the air supply 4 Manual override When the manual override is oper...

Page 10: ...port valve is required How to Use Plug Connector When attaching and detaching a connector first shut off the electric power and the air supply Also crimp the lead wires and sockets securely 1 Attachi...

Page 11: ...ocket s hook with a stick having a thin tip approx 1 mm If the socket is used again spread the hook outward Common Connector Assembly Wiring When ordering common connector assemblies alone wiring shou...

Page 12: ...be used again cut off the portion which has been chewed before reusing it If the chewed portion of the tube is used as is this can cause trouble such as air leakage or difficulty in removing the tube...

Page 13: ...12 SX3000 OMM0002 B...

Page 14: ...13 SX3000 OMM0002 B...

Page 15: ...brasion spool ass y ring in the case of rubber seal Poor operation or adherence Excessive amount of lubricant Higher voltage or wrong coil used Faulty wiring Poor contact at contactor wire or connecti...

Page 16: ...cation was suspended temporary Water splashed directely Strong impact was given Alien substance such as drain and particle got into Drain or garbage invaded a valve Reduce the amount of lubricant to t...

Page 17: ...kyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 201...

Reviews: