-23-
No.LFE****-OMZ0013
<Operation>
1. Selection of output mode
Press the
or
button in function selection mode to display [F 1] on the main screen.
The sub screen alternately displays [oUt1] and the currently set output mode.
Press the
button.
Sub screen
Press the
or
button to select the desired output mode.
Press the
button to set. Move on to the setting of reversed output.
*: If a button operation is not performed for 30 seconds during the change of setting, the display will flash.
*: When the accumulated pulse output is selected, the indicator light will turn off.
2. Setting of reversed output
Sub screen
Press the
or
button to select reversed output mode.
Press the
button to set. Move on to the input of set values(ON-OFF point).
*: If you selected accumulated pulse output mode, move on to the selection of display color (page 27).