Doc.No.LFE****-OMZ0013 

 

 

 

 

 

 

 

 
 

Product Name 

 

Flow Monitor 

 

Model/ Series/ Product Number 

 

LFE0### 

 

 

 

 

 

 

 

 

 

 

 

 

 

SMC Corporation 

 

 

 

Summary of Contents for LFE0 Series

Page 1: ...Doc No LFE OMZ0013 Product Name Flow Monitor Model Series Product Number LFE0 SMC Corporation ...

Page 2: ...T1 22 F 2 Setting of OUT2 30 F 3 Response Time 36 F10 Sub screen display 37 F20 External input 41 F22 Analogue Output in free range 42 F30 Accumulated flow value hold 44 F80 Power saving mode 45 F81 Security Code Request 46 F82 Input of line names 47 F90 Setting of all functions 48 F96 Input value check 49 F97 Selection of copy function 50 F98 Output check 53 F99 Reset to the default settings 54 O...

Page 3: ... equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to remo...

Page 4: ... failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from this 1 year warranty A vacuum pad is a consumable part so it is warranted for a year after it is delivered Also even within the warranty period the wear of a product due to the use of the vacuu...

Page 5: ...n result Do not Do not operate the product outside of the specifications Do not use for flammable or harmful fluids Fire malfunction or damage to the product can result Please check the specifications before use Do not Do not use in an atmosphere containing flammable or explosive gases Fire or an explosion can result The product is not designed to be explosion proof Do not Do not use the product f...

Page 6: ...afety cannot be assured in the case of unexpected malfunction Handling Precautions Follow the instructions given below for selecting and handling The instructions on design and selection installation wiring environment adjustment operation maintenance etc described below must be followed Product specifications Use the specified voltage Otherwise failure or malfunction can result Insufficient suppl...

Page 7: ...of the wire to peel off or breakage of the wire If the lead wire can move fix it near the body of the product The recommended bend radius of the lead wire is 6 times the outside diameter of the sheath or 33 times the outside diameter of the insulation material whichever is larger Replace the damaged lead wire with a new one Wire correctly Incorrect wiring can cause malfunction or damage the produc...

Page 8: ...load which generates surge voltage When a surge generating load such as a relay or solenoid is directly driven use the product with a surge absorbing element built in The product is CE marked but not immune to lightning strikes Take measures against lightning strikes in the system Mount the product in a location that is not affected by vibration or impact Failure or malfunction may result Do not u...

Page 9: ...d flow setting be sure to check for the influence on the other components Stop the control system for setting if necessary Do not touch the LCD during operation The display can vary due to static electricity Maintenance Confirm safety by turning off the power supply and stopping the flow before performing maintenance There is a risk of unexpected malfunction Perform regular maintenance and inspect...

Page 10: ...er ZS 26 C Waterproof seal with screw Protective cover only ZS 26 01 Please order panel mount adapters etc separately Power supply output lead wire ZS 40 W Lead wire length 2 m Sensor connector e con ZS 28 C 5 1 pcs Copy lead wire ZS 40 Y Connect up to 10 copy destination units Remote type monitor Option1 Panel type Option2 Connector Display unit Symbol Instantaneous flow Accumulated flow M L min ...

Page 11: ...tput status of OUT1 and OUT2 LED is ON Orange when OUT1 is ON Sub screen Displays the accumulated flow set value peak bottom value and more Units indication Indicates the unit currently selected UP DOWN button Selects the mode and the display shown on the Sub display or increases decreases the ON OFF set value SET button Press this button to change the mode and to set a value Back Units indication...

Page 12: ...s D Display flow range The range of flow rates that can be displayed to satisfy the specifications F F S full span full scale This means full span or full scale and indicates maximum variation width at rated value For example when analogue output is 1 to 5 V F S 5 V 1 V 4 V Reference 1 F S 4 V 1 0 04 V H Hysteresis The difference between ON and OFF points used to prevent chattering Hysteresis mode...

Page 13: ...ON or OFF In the ON condition any connected load will be powered In the OFF condition there will be no power supplied to the load An output showing such behavior is called switch output T Temperature characteristics Indicates the change in the display value and analogue output caused by ambient temperature or fluid temperature changes W Water hammer Water hammer or impact pressure is a pressure su...

Page 14: ...enter After the product makes contact with the panel the screws should be further tightened 1 4 to 1 2 turn Cut out dimensions for panel mounting See page 66 for panel cut out dimensions How to remove the panel mount adapter The product with panel mount adapter can be removed from the panel after removing the two screws and by disconnecting the hooks on both sides This can be done by inserting a s...

Page 15: ...s straight into the body until it clicks When removing the connector press down the lever to release the hook from the housing and pull the connector straight out Sensor connector 1 DC Brown 2 N C Unused Do not connect to Black 3 DC Blue 4 INPUT White flow sensor 1 to 5 V Power supply output connector COPY Grey OUT2 White OUT1 Black DC Blue DC Brown ...

Page 16: ...ulator outside diameter ZS 28 C 5 Included in the product Grey ø 1 6 ø 2 0 Do not cut the insulator The core of the corresponding colour shown in the table below is put into the pin of the number stamped on the connector for sensor connection to the back Number stamped on connector Lead wire core colour 1 Brown 2 Not used 3 Blue 4 White When using the lead wire with M12 connector included with the...

Page 17: ...rrent output type LFE0D Max 28 V 80 mA Internal voltage drop 1 V max Analogue output 1 to 5 V Output impedance 1kΩ Max 28 V 80 mA Internal voltage drop 1 V max Analogue output 4 to 20mA Load impedance 50 to 600 Ω Precautions before use of the accumulated pulse output 1 The minimum pulse width is set to 50 ms when the accumulated pulse output has been selected 2 When accumulated pulse output is sel...

Page 18: ...he setting or setting other functions Be sure to select the correct sensor to be connected Page 21 Detected flow rate and switch operation hysteresis mode Set ON and OFF points of the switch output When the flow exceeds the set value P_1 the switch will be turned on When the flow falls below the set value P_1 by the amount of hysteresis H_1 or more the switch will be turned off Flow rate L min Tim...

Page 19: ...ton to completed the setting The Flow switch turns on within a set flow range from P1L to P1H during window comparator mode Set P1L the lower limit of the switch operation and P1H the upper limit of the switch operation following the instructions given above When reversed output is selected the main screen displays n1L and n1H When 2 output specification LFE0A LFE0B is used P_2 or n_2 is displayed...

Page 20: ... type F 1 Setting of OUT1 Page 22 Item Description Default setting Output mode Selects the switch output type from Instantaneous flow either hysteresis or window comparator mode accumulated flow accumulated pulse Hysteresis mode Reverse output Selects which type of switch output is to be used normal or reversed Normal output Set value Sets the ON and OFF point of the switch output 50 of rated flow...

Page 21: ...sensor output voltage F97 Selection of copy function Page 50 OFF F98 Output check Page 53 OFF F99 Reset to the default settings Page 54 OFF Other settings Page 55 The key lock has not been set Sub screen In measurement mode the display of the sub screen can be temporarily changed by pressing the or buttons After 30 seconds it will automatically reset to the display selected in F10 Example for 20 L...

Page 22: ...d for 2 seconds or longer F 0 is displayed The sub screen displays RANGE and the currently selected flow rate alternately Press the button Sub screen Press the or button to select the sensor to be connected Press the button to confirm Return to function selection mode F 0 Sensor selection is completed 20L min 100L min 200L min ...

Page 23: ...ccumulated pulse PLS 2 Setting of reversed output 1_P 1_N Page 23 3 Input of set values Setting of P_1 n_1 H_1 Page 24 Setting of P1L n1L P1H n1H H1 Page 24 Setting of Add dEC P1AH n2AH P1dH n1dH Page 25 4 Select of display color SoG SoR REd GRN Page 30 5 Completed F 1 Setting of OUT1 is complete By switching to reversed output the display color will change in relation to the setting ...

Page 24: ...he button to set Move on to the setting of reversed output If a button operation is not performed for 30 seconds during the change of setting the display will flash When the accumulated pulse output is selected the indicator light will turn off 2 Setting of reversed output Sub screen Press the or button to select reversed output mode Press the button to set Move on to the input of set values ON OF...

Page 25: ...e and hysteresis settings limit each other Output mode b When window comparator output mode is selected The sub screen displays the set value Change it with or button When reversed output is selected the main screen displays n1L Press the button to set Move on to the input of set value for P1H or n1H The sub screen displays the set value Change it with or button When reversed output is selected th...

Page 26: ...d output mode Add dEC Press the button to set Move on to the input of set values Accumulated increment mode Accumulated decrement mode The sub screen displays the set value Change it with or button When reversed output is selected the main screen displays n1AH The sub screen displays the set value Change it with or button When reversed output is selected the main screen displays n1dH Continued ...

Page 27: ...ext digit to the right After the input of the first 3 digits is completed press the button for 1 second of longer The flashing will stop Press the button to again to confirm the values of the first digits and move on to the input of the next 6 digits Setting of the lower 6 digits After the input of the lower 6 digits is completed press the button for 1 second of longer to confirm Press the button ...

Page 28: ... set to change depending upon the status of OUT1 Sub screen Press the or button to select the display color Press the button to set Return to function selection mode 5 Completed F 1 Setting of OUT1 complete ON Green ON Red OFF Red OFF Green Normally Red Normally Green ...

Page 29: ...ed pulses to obtain the accumulated flow based on the accumulated volume per pulse page 62 Count up from 0 Turns ON when the set value is reached Return to 0 by reset Count down from set value Turns ON when 0 is reached Return to the set value by reset Accumulated pulse output mode Hysteresis H_1 H_2 Hysteresis H1 H2 Hysteresis H1 H2 Instantaneous flow Accumulated flow Accumulated flow Time Time I...

Page 30: ...eresis mode Instantaneous flow n1d n2d n1A n2A A pulse will be output by each accumulated pulse conversion value n1H n2H Count down from the set value Turns off when 0 is reached Return to the set value by reset Window comparator mode Accumulated increment output mode Accumulated decrement output mode Accumulated pulse output mode Time Time Time Reversed output Accumulated flow Accumulated flow ...

Page 31: ...mode Hysteresis HYS Window comparator WIN Accumulated output ACCUMU Accumulated pulse output PLS Hysteresis tHYS Window comparator tWIN 2 Setting of reversed output 2_P 2_N Page 31 3 Input of set values Setting of P_2 n_2 H_2 Page 32 Setting of P2L n2L P2H n2H H2 Page 32 Setting of Add dEC Page 33 tn tP H_t setting Page 34 tnL tPL tnH tPH Ht setting Page 34 4 Completed F 2 Setting of OUT2 complete...

Page 32: ...ess the or button to select the desired output mode Press the button to set Move on to the setting of reversed output Hysteresis comparator mode for fluid temperature are items which are not used for this product 2 Setting of reversed output Sub screen Press the or button to select reversed output mode Press the button to set Move on to the input of set values ON OFF point When the accumulated pul...

Page 33: ...e and hysteresis settings limit each other Output mode b When window comparator output mode is selected The sub screen displays the set value Change it with or button When reversed output is selected the main screen displays n2L Press the button to set Move on to the input of set value for P2H or n2H The sub screen displays the set value Change it with or button When reversed output is selected th...

Page 34: ...n displays the set value Change it with or button When reversed output is selected the main screen displays n2AH The sub screen displays the set value Change it with or button When reversed output is selected the main screen displays n2dH For details refer to c When accumulated output mode is selected on page 31 Press the button to set Return to function selection mode F 2 Setting of OUT2 complete...

Page 35: ...e for fluid temperature is selected The sub screen displays the set value Change it with the or button When normal output is selected the main screen displays tPL Press the button to confirm Move on to the input of set values for tPH or tNH The sub screen displays the set value Change it with the or button When normal output is selected the main screen displays tPH Press the button to confirm Move...

Page 36: ... 35 No LFE OMZ0013 List of output modes for fluid temperature ...

Page 37: ... from chattering Operation Press the or button in function selection mode to display F 3 on the main screen The sub screen alternately displays RES and the current set value Press the button Sub screen Press the or button to select the response time Press the button to set Return to function selection mode F3 Response time setting complete 2 s 5 s 0 5 s 1 s ...

Page 38: ...ture display Shows fluid temperature Temperature bottom display The bottom value of fluid temperature is displayed Temperature peak display The peak of fluid temperature is displayed OFF Displays nothing Operation Press the or button in function selection mode to display F10 on the main screen The sub screen alternately displays SUb and the current set value Press the button The sub screen display...

Page 39: ...tantaneous flow Main screen Instantaneous flow Main screen Instantaneous flow Main screen Instantaneous flow Main screen Instantaneous flow Sub screen Display of set value P_1 Sub screen Display of set value P1H Sub screen Display of set value N1H Main screen Instantaneous flow Main screen Instantaneous flow Sub screen Display of set value N_1 Sub screen Display of set value P1L Sub screen Display...

Page 40: ...r the power is supplied When the option to memorize the cumulated value is selected it will start from the memorized value Pressing the button for 1 second resets the accumulated value to 0 Accumulated decrement mode The cumulative value decreases from the set value according to the instantaneous flow When the value exceeds 999999L the higher 3 digits 1 5s and lower 6 digits 3s are displayed alter...

Page 41: ... on page for how to input the line name page 47 If a fluid temperature sensor is attached the fluid temperature can be displayed as well The left most digit shows Centigrade oC The sub display can be turned off Main screen Instantaneous flow Main screen Instantaneous flow Line name display mode Sub screen Display of line name Sub screen Turned off Sub screen off mode ...

Page 42: ... 41 No LFE OMZ0013 F20 External input This item is not used for this specification ...

Page 43: ...the rated range Operation Press the or button in function selection mode to display F22 on the main screen The sub screen alternately displays AnA and the current set value If the analogue output is not present the sub screen alternately displays AnA and Press the button Sub screen Press the button When the FLoW is selected Press the button when the tEMP is selected F22 Setting of analogue output ...

Page 44: ...tered flow value can be in the range 10 rated flow to the upper display limit Press the button to set Return to function selection mode F22 Analogue output setting complete Turn the power off and turn it on again if the setting of analogue output is changed 2 20 24 Press the button Flow rate L min 20L min Analogue 1 5V ...

Page 45: ...es 2 million minutes 3 8 years Operation Press the or button in function selection mode to display F30 on the main screen The sub screen displays SAVE and the current set value in turn Press the button Sub screen Press the or button to select the accumulate flow value hold Press the button to set Return to function selection mode F30 Setting of accumulated flow value hold complete Data is stored e...

Page 46: ...play F80 on the main screen The sub screen alternately displays dSP and the current set value Press the button Sub screen The display can be turned off to save power Press the or button to select the power saving mode setting Press the button to set Return to function selection mode F80 Setting of power saving mode complete In power saving mode the decimal points on the main display will flash Whe...

Page 47: ...nd security code request is invalid Operation Press the or button in function selection mode to display F81 on the main screen The sub screen displays PiN and the current set value in turn Press the button Sub screen Press the or button to select valid or invalid for the security code request Press the button to set Return to function selection mode F81 Setting of security code request complete In...

Page 48: ...git changes like Space A b C X y Z 0 1 8 9 Select the letter you want to display Press the button Less than 1 sec The next digit to the right will flash and can be edited Follow the same procedure for the remaining digits After inputting 6 digits Press the button for 1 seconds or longer Flashing stops Press the button to set Return to function selection mode F82 Line name setting complete When a d...

Page 49: ...he or button in function selection mode to display F90 on the main screen Press the button Sub screen OFF ON F 0 F82 All functions can be set one after the other Setting method depends on the setting of each function Press the button for 2 seconds or longer to return to measurement mode Return to function selection mode F90 Setting of all functions complete Not used Used Press the button ...

Page 50: ...utton Displays the voltage value currently selected on the sub screen Press the button to select INPUT 1 or INPUT2 Press the button to confirm Return to the function selection mode F96 Input value check is complete This product uses only INPUT1 In INPUT2 the sensor signal is not connected If zero is input to INPUT1 and INPUT2 the input displayed may not be zero due to the adjustment error of the e...

Page 51: ...available The set value can be copied up to 10 units simultaneously Connection The power supply should be turned off before connecting the flow monitors Connect the copy source flow monitor and the copy destination flow monitors with copy lead wire ZS 40 Y and turn on the power supply The copy source flow monitor is the flow monitor from which the setting is copied The copy destination flow monito...

Page 52: ...rent set value flashes on the sub screen Sub screen Press the or button to select copy function ON ONLOC OFF F97 Selection of copy function complete The copy ready status is maintained held even if the power supply is turned off Press the button to start copying continued on next page Press the button Lock the key after the setting is copied to the copy destination units Not used ...

Page 53: ...dy status is maintained held even if the power supply is turned off When completing copy function press the and buttons simultaneously for 1 second at least F97 Selection of copy function is complete Return to measurement mode If the copy to the copy destination flow monitor is not completed it is detected as a copying function sending receiving error Press the and buttons simultaneously for 1 sec...

Page 54: ... changes NoRMAL FoRCE Forced ON OFF of OUT1 Sub screen Changing the display between ON and OFF using or button also changes the output status Press the button Forced ON OFF of OUT2 Sub screen Analogue output ON 5V or 20mA OFF 1V or 4mA Return to function selection mode F98 Setting of output check complete Press the button for 2 seconds or longer to return to measurement mode An increase or decreas...

Page 55: ...e main screen Press the button Sub screen Press the or button to display ON Press the and button simultaneously for 5 seconds to restore the default settings Press the button for 1 second or longer the display returns to measurement mode without changing the setting The device automatically returns to function selection mode F99 Reset to the default settings complete Not used Used ...

Page 56: ...t Security code used to cancel key lock Invalid Not required Valid Required When setting a key lock The following key lock settings are the same for enabling disabling the security code request F81 1 Press the button for 5 seconds or longer in measurement mode The current setting UNLoC flashes on the sub screen Sub screen 2 Press the or button to select locking LoC 3 Press the button to select the...

Page 57: ...e right flash If the button is pressed on the far right digit the hundreds digit will flash 5 After the input is complete press and hold the button for 1 second or longer The security code will be confirmed If no key operation is performed for 30 seconds during input or change of the security code the display will return to measurement mode with LoC status If the security code entered is wrong FAL...

Page 58: ...r in measurement mode The current setting will flash as LoC on the sub screen 2 Press the or button to select Unlock UnLoC 3 After the button is pressed the system prompts you to enter the security code 4 Key in your security code 5 Press and hold the button for 1 second or longer to enter the security code 6 When UNLoC is displayed in the sub screen press the and buttons simultaneously for 5 seco...

Page 59: ...e settings for the product are retained in memory prior to the power loss or de energizing of the product The output condition is also recoverable to that prior to the power loss or de energizing However this may change depending on the operating environment Therefore check the safety of the whole installation before operating the product ...

Page 60: ...completely filled with fluid There are bubbles in the fluid path Place the piping in the correct position for helping discharge air bubbles Pulsation in the flow It is recommended to place a component to reduce pulsating flow or a tank to reduce pressure fluctuation or replace the piping with elastic tubing such as a rubber hose Installed in area not suitable for mounting Check the products instal...

Page 61: ...t be set OUT1 OUT2 set value does not go down Hysteresis is too large Check the detected flow rate setting and the hysteresis and verify that the hysteresis width is not too large for the detected flow The detected flow rate has been set to 50 of the rated value and the hysteresis set to 5 of the rated value before shipment of the product from the factory When setting the hysteresis width to a nar...

Page 62: ... 1 2 Reduce the flow within the display flow range Reverse flow error Sensor disconnection error The flow is flowing in the reverse direction of the setting The remote sensor is not connected to the monitor Apply flow in the correct direction Connect the sensor Excessive accumulated flow Alternately displays 999 and 999999 The accumulated flow range has been exceeded Reset the accumulated flow Thi...

Page 63: ...aximum load current 80 mA Maximum applied voltage 28 VDC Internal voltage drop NPN 1 V max at 80 mA load current PNP 1 5 V max at 80 mA load current Response time 2 Can be selected from 0 5 s 1 s 2 s 5 s Output protection Short circuit protection Output Mode Select from Hysteresis mode Window comparator mode Accumulated output mode or Accumulated pulse output mode Analogue output Response time 3 L...

Page 64: ...It is possible to select the function to memorize it Select the interval of 2 min or 5min When a 5min interval is selected the maximum life of the electronic memory element is 1 million writes if energized for 24 hours 5min x 1 million times 5 million minutes Approx 9 5 years If accumulated value hold is used calculate the life based on the operating conditions not to exceed the life of the produc...

Page 65: ...low Analogue output A B C Voltage output 1 V 1 1 V 5 V Current output 4 mA 4 4 mA 20 mA Model Rated flow L min Minimum Maximum LFE1 0 5 20 LFE2 2 5 100 LFE3 5 200 Maximum rated flow Minimum rated flow Flow rate 0 A B Output C Out of range ...

Page 66: ... 65 No LFE OMZ0013 Dimensions Front protective cover Panel mount adapter R ...

Page 67: ... 66 No LFE OMZ0013 Cut out dimensions for panel mounting The thickness of the panel is 0 5 to 0 8mm with a waterproof seal 0 5 to 6mm Dimensions of power supply output lead wire ZS 40 W ...

Page 68: ...okyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL https www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2022 SMC Corporation All Rights Reserved ...