5.2 JOG Mode
JOG operation can be executed without host command. Use this function with the forced stop disabled.
(1)
The “JOG Mode” window can be displayed by selecting “Jog
Mode” from the “Test Mode” menu in the
setup software
.
(2)
Click “OK”.
(When using this function, all external input signal operation will be disabled. If controlling using a PLC
or other upper device, please turn off the power and reset the device before use.)
(3)
Check actuator JOG operation using [Forward (CCW)] and [Reverse (CW)] in JOG mode.
(if operation is not correct, please check wiring and parameters).
When performing JOG operation in the setup software, the rotation direction of the actuator does not
change if you change the setting of parameter PA14 (Rotation direction selection).
The
actuator moves in the direction of [Forward (CCW)] button and [Reverse (CW)] button.
(4)
If the selection “LSP and LSN are automatically turned ON” is not checked, an alarm will occur (if
checked, the stroke end signals “LSP” & “LSN” will be automatically turned ON when this window is
open).
Item
Setting range
Unit
Description
Motorspeed
0 to allowable actuator speed
r/min
Set the command speed of the servo motor for execution of positioning
(motor rotations/minute).
Acceleration
/deceleration time
0 to 50000
ms
Set the time until the servo motor reaches/stops to the rated speed (3000
r/min).