12.2 Alarm details
Controller
Setting Software
(code)
Teaching
box
G
rou
p
How to
deactivate
Alarm contents/ Countermeasure
Drive data value
is wrong
(01-048)
Operation
data error
B
RESET
input
<Contents>
The step data is in-correct for the following conditions
(Assignable value range)
(1) "Area1" < "Area2"
(If both "Area1 and Area2" is 0, the alarm will not be
activated.)
(2) "Trigger LV" ≤ "Pushing force"
(If Pushing force< "Trigger LV" at the time of "Pushing
force" = 0, the alarm will not be activated.)
(3) Minimum speed of the
electric actuator ≤ "Pushing
speed"
≤ "Speed"
(4) "Pushing speed" ≤ Maximum pushing speed of the
electric actuator
(5) Pushing force
≥ Minimum pushing force of the electric
actuator
(6) Basic parameters "Max force"
≥ Minimum pushing force
of the electric actuator
(7) Basic parameters "Max force"
≥ "Trigger LV"
<Countermeasure>
Modify the step data and basic parameters setting.
Caution
Please confirm this pushing force and minimum speeds
of Data maximum speed and 0 or more of the electric
actuator with the electric actuator manual or the
catalog.
The Parameter
value is incorrect
(01-049)
System
parameter
error
B
RESET
input
<Contents>
The basic parameter is not correct for the following
condition: (Assignable value range)
(1) Stroke (-) < Stroke (+)
(2) W-Area 1 < W-Area2
(If both W-Area1 and W-Area2 is 0, the alarm will not
be activated.)
(3) Maximum pushing force < Maximum pushing force of
the electric actuator
<Countermeasure>
Modify the basic parameter setting.
Caution
Please refer to the manual or the catalogue of the
electric actuator for the max/ min pushing force / speed
for the electric actuator.
The deceleration
value is too
small.
(01-050)
Small
Dec
B
RESET
input
<Contents>
Step data in which a deceleration speed exceeding the
stroke limit is specified.
<Countermeasure>
Modify the Deceleration value to a value with a sufficient
margin so that the electric actuator can stop within the
stroke limit.