- 41 -
No.JXC
※
-OMX0011-A
7.3
Return to origin parameter
The
"
Return to origin parameter
"
is the setting data for the return to origin operation.
Details of Return to origin parameter
Activation: "XX" = Become effective just after recorded into the controller
"X" = Become effective after restarting the controller
"-" = The parameter cannot be changed (fixed value)
Parameter name
Range
Description
Activation
ORIG direction
1 to 2
Sets the direction of return to origin operation. Note1)
1. CW
2. CCW
X
Return to origin mode
1 to 2
The setting for the return to origin operation.
1: Pushing origin operation [Stop]
2: Limit switch origin [SW]
XX
ORIG limit
Note2)
A pushing force level at which to set the origin.
XX
ORIG time
Fixed value
This is a fixed value for the controller.
(Do not change the setting)
-
ORIG speed
Note2)
The allowable speed to move to origin.
XX
ORIG ACC/ DEC
Note2)
The acceleration and deceleration during return to origin
operation.
XX
Creep speed
Fixed value
This is a fixed value for the controller.
(Do not change the setting)
-
ORIG sensor
0 to 2
The setting for the ORIG sensor.
0. The origin sensor is not effective. [Disable]
1. The origin sensor is N.O type. [N.O].
2. The origin sensor is N.C type. [N.C].
XX
ORIG SW DIR
Fixed value
This is a fixed value for the controller.
(Default value is "0")
-
Undefined parameter
No.21
Fixed value
This is a fixed value for the controller.
(Default value is "0")
-
Note1) When power is applied again after changing Return to origin parameter "Return to Origin Direction", the SETON
output is turned OFF.
Perform return to origin operation again.
Note2) The actuator model determines the available input values. Refer to the operation manual of the actuator for details.