HRX-OM-M091
Chapter 4 MODBUS communication function
4.10 Register Map
HRS Series
4-18
4.10.4 Status
flag
The status of the product is read by the following assignment.
Name Status
flag
Bit
15
14
13 12 11
10
9
8
7
6
5
4
3 2 1 0
Bit
Name
Explanation
0 Run
flag
Run status (Include the independent operation of the
pump)
0= Stop
1=Run
1
Operation stop alarm flag
Operation stop alarm given off status
0= Not occurred
1= Operation stop alarm given
off
2
Operation continued alarm
flag
Operation continued alarm given off status
0= Not occurred
1= Operation continued alarm
given off
3 Unused
4
Press Unit flag
Pressure unit set status
0=MPa
1=PSI
5 Remote
status
flag
Remote status
0= Other than SERIAL mode
1=SERIAL mode
6 Unused
7 Unused
8 Unused
9
Completion of preparation
(TEMP READY) flag
Completion of preparation (TEMP READY) status
0= Condition isn’t formed
1= Condition is formed
10 Temperature
unit
flag
Temperature unit set status
0= Centigrade
(
o
C
)
1= Fahrenheit
(
o
F
)
11
Run timer flag
Run timer set status
0=Not set
1= Set
12
Stop timer flag
Stop timer set status
0= Not set
1=Set
13
Reset after power failure flag
Reset after power failure set status
0= Not set
1= Set
14 Anti-freezing
flag
Anti-freezing set status
0= Not set
1= Set
15
Automatic fluid filling flag
Automatic fluid filling condition
0= Stop
1= Fluid
∗
The signal of the product without an option
[Automatic filling] also changes.