Specifi cations:
Air-cooled Refrigeration
Model
HRR012-A
HRR018-A
HRR024-A
HRR030-A
Cooling method
Air-cooled refrigeration
Refrigerant
R410A (HFC)
Refrigerant charge
[kg]
0.38
0.47
Control method
PID control
Ambient temperature/Humidity/Altitude
∗
1, 13
Temperature: 5 to 40
°
C, Humidity: 30 to 70 %, Altitude: less than 3000 m
Cir
culating fl
uid
system
Circulating fl uid
∗
2
Tap water, 15 % ethylene glycol aqueous solution
Set temperature range
∗
1
[
°
C]
10 to 35
Cooling capacity (50/60 Hz)
∗
3
[W]
1000/1200
1600/1800
2000/2400
2500/3000
Heating capacity (50/60 Hz)
∗
4
[W]
450/500
550/700
Temperature stability
∗
5
[
°
C]
±
0.1
Pump capacity (50/60 Hz)
∗
6
[MPa]
0.13 (at 7 l/min)/0.18 (at 7 l/min)
For Option T: 0.42 (at 10 l/min)/0.4 (at 14 l/min)
For Option MT: 0.32 (at 10 l/min)/0.32 (at 14 l/min)
Rated fl ow (50/60 Hz)
∗
7
[l/min]
7/7 For Options T, MT: 10/14
Flow display range
[l/min]
3 to 16
Electric conductivity display range
[
μ
S/cm]
2 to 48 (Only for Option DM)
Electric conductivity setting range
[
μ
S/cm]
5 to 45 (Only for Option DM)
Particle fi lter nominal fi ltration rating [
μ
m]
5
Bypass valve
Installed
Tank capacity
[L]
Approx. 4
Outlet, Return port size
Rc1/2
Drain port size
Rc1/4, With cap
Leakage protection
Drain pan (With water leakage sensor)
Fluid contact material
Stainless steel, Copper (Heat exchanger brazing)
∗
11
, Brass
∗
16
, SiC,
Alumina ceramic, Carbon, PP, PE, POM, PA, FKM, EPDM, PVC,
PPS, AS, Fluoropolymer
∗
12
, Ion exchange resin
∗
12
Electrical system
Power supply
Single-phase 200 to 230 VAC, 50/60 Hz, Allowable voltage range
±
10 %
∗
14
Circuit protector
[A]
10 For Options T, MT: 15
Applicable earth leakage breaker capacity
∗
8
Rated current: 10 A For Options T, MT: 15 A
Sensitivity current: 30 mA
Cable quantity x Size (Including grounding cable)
∗
15
3 cores x 14 AWG (3 cores x 2.0 mm
2
)
Rated operating current
(50/60 Hz)
∗
3
[A]
3.6/4.0
3.6/4.3
5.2/5.8
5.5/6.2
For Options T, MT
4.7/6.2
4.7/6.5
6.3/8.0
6.5/8.3
Rated power consumption
(50/60 Hz)
∗
17
[kW(kVA)]
0.6/0.8 (0.7/0.8)
0.7/0.9 (0.7/0.9)
0.9/1.2 (1.1/1.2)
1.0/1.2 (1.1/1.3)
For Options T, MT
0.9/1.2 (0.9/1.2)
0.9/1.3 (1.0/1.3)
1.2/1.6 (1.3/1.6)
1.3/1.6 (1.3/1.7)
Communication function
Contact input/output, Serial RS-485/RS-232C
Noise level (50/60 Hz)
∗
9
[dB]
59/60
59/60
61/64
61/64
Accessories
∗
18
Power supply connector, Particle fi lter element and maintenance handle, Operation manual
Weight
∗
10
[kg]
40
46
∗
1 It should have no condensation. During seasons or in locations where
the ambient temperature is likely to fall below freezing point, please con-
tact SMC for that case.
∗
2 If tap water is used, use water that conforms to Water Quality Standards
of the Japan Refrigeration and Air Conditioning Industry Association
(JRA GL-02-1994 cooling water system - circulating type - make-up wa-
ter).
∗
3
q
Ambient temperature: 2 5
°
C,
w
Circulating fl uid temperature: 2 0
°
C,
e
Circulating fl uid rated fl ow,
r
Circulating fl uid: Tap water,
t
Power
supply: 200 VAC,
y
Piping length: Shortest
For models with high-pressure pump mounted (Options T, MT), the cool-
ing capacity will decrease by 300 W.
∗
4
q
Ambient temperature: 2 5
°
C,
w
Circulating fl uid temperature: 2 0
°
C,
e
Circulating fl uid rated fl ow,
r
Circulating fl uid: Tap water,
t
Power
supply: 200 VAC,
y
Piping length: Shortest
∗
5 Temperature at the thermo-chiller outlet when the circulating fl uid fl ow is
rated flow, and the circulating fluid outlet and return port are directly
connected. Installation environment and the power supply are within
specifi cation range and stable.
∗
6 The capacity at the thermo-chiller outlet when the circulating fl uid tem-
perature is 20
°
C.
∗
7 Required fl ow rate for maintaining the cooling capacity or temperature
stability
The specifi cation of the cooling capacity and the temperature stability
may not be satisfi ed if the fl ow rate is lower than the rated fl ow.
∗
8 Purchase an earth leakage breaker with sensitivity current of 30 mA/pow-
er supply 200 VAC separately.
∗
9 Front: 1 m, height: 1 m, stable with no load, Other conditions
J
See
∗
3.
∗
10 Weight in the dry state without circulating fl uids
The weight will increase by 1 kg when Option DM (With electric con-
ductivity control fu Applicable to DI water piping) is selected.
The weight will increase by 5 kg when Option T (High-pressure pump
mounted) or MT (Applicable to DI water High-pressure pump
mounted) is selected.
∗
11 Copper and brass are not included when Option M (Applicable to DI
water piping) or MT (Applicable to DI water High-pressure
pump mounted) is selected.
∗
12 For Option DM (With electric conductivity control fu Applicable
to DI water piping)
∗
13 If the product is used at altitude of 1000 m or higher, refer to “
∗
For al-
titude of 1000 m or higher” on page 25.
∗
14 No continuous voltage fl uctuation
∗
15 To be prepared by the customer
∗
16 For Option T (High-pressure pump mounted), this material is included.
∗
17
q
Ambient temperature: 2 5
°
C,
w
Circulating fl uid temperature: 2 0
°
C,
e
Circulating fl uid rated fl ow,
r
Circulating fl uid: Tap water,
t
Power supply:
200 VAC,
y
Piping length: Shortest,
u
At the rated cooling load applied
∗
18 For Option DM (With electric conductivity control fu Applicable
to DI water piping), a DI fi lter is attached.
For pipe thread type F, a G thread conversion fi tting set is attached.
For pipe thread type N, an NPT thread conversion fitting set is at-
tached.
10
Thermo-chiller/Rack Mount Type
HRR
Series