FS-8700-130 Notifier NCA2-NFS2-3030 Manual
Page 9 of 23
Parameter
Addresses
For each SLC loop per Node
Memory Type :
Detector ; Module
Fire Alarm
1
– 159
Security Life
160
– 318
Life Critical
319
– 477
Medical Emergency
478
– 636
Security Alarm
637
– 795
Critical Process
796
– 954
Supervisory
955 - 1113
Disabled
1114
– 1272
Prealarm
1273
– 1431
Active
1432
– 1590
ON/OFF
1591
– 1749
Memory Type :
Detector_Trouble; Module_Trouble
Troubles/Faults
1
– 159
Parameter
Addresses
For each Node
Memory Type :
Node_Trouble
Troubles/Faults
1
– 508
Memory Type :
Panel
Panel
(Maximum12 Boards and 8 Panel circuits per Board )
Hardware address memory address
Board 1 panel 1 1
Board 1 panel 2 2
Board 2 panel 1 9
-----
-----
Board 12 panel 8 96
)
Fire Alarm
1
– 96
Security Life
97 - 192
Life Critical
193 - 288
Medical Emergency
289 - 384
Security Alarm
385 - 480
Critical Process
481 - 576
Supervisory
577 - 672
Disabled
673 - 768
Prealarm
769 - 864
Active
865 - 960
ON/OFF
961 - 1056
Memory Type :
Panel_Trouble
Troubles/Faults
1
–96
Memory Type :
Bell_Trouble
Troubles/Faults
1-4
Table 1
– Memory Mapping Address Structure.