background image

 

FS-8700-130 Notifier NCA2-NFS2-3030 Manual 

Page 21 of 23 

System Trouble         

Address 

 

System Trouble         

Address 

REMOTE DISPLAY 8 NO ANSWER                   172 

 

TERM SUPERVISORY                            

426 

REMOTE DISPLAY 9 NO ANSWER                   173 

 

CRT SUPERVISORY                             

427 

REMOTE DISPLAY 10 NO ANSWER                 174 

 

TERMINAL SUPERVISORY PATH IS INTERRUPTE      428 

REMOTE DISPLAY 11 NO ANSWER                 175 

 

NVRAM BATTERY TROUBLE                       

429 

REMOTE DISPLAY 12 NO ANSWER                 176 

 

NCM PIEZO BATTERY FAILURE                   

430 

REMOTE DISPLAY 13 NO ANSWER                 177 

 

BATTERY(S) NOT CONNECTED OR DEFECTIVE        431 

REMOTE DISPLAY 14 NO ANSWER                 178 

 

BATTERY CHARGER DETACHED                    

432 

REMOTE DISPLAY 15 NO ANSWER                 179 

 

BATTERY                                     

433 

REMOTE DISPLAY 16 NO ANSWER                 180 

 

TM4 DISABLED                                

434 

REMOTE DISPLAY 17 NO ANSWER                 181 

 

UP/DOWN LOAD IN PROGRESS _ ACS DISABLED      435 

REMOTE DISPLAY 18 NO ANSWER                 182 

 

NO DEV INST ON L1                           

436 

REMOTE DISPLAY 19 NO ANSWER                 183 

 

ADV WALK TEST                               

437 

REMOTE DISPLAY 20 NO ANSWER                 184 

 

PROG MODE ACTIVATED                         

438 

REMOTE DISPLAY 21 NO ANSWER                 185 

 

LOADING..NO SERVICE                         

439 

REMOTE DISPLAY 22 NO ANSWER                 186 

 

BASIC WALK TEST                             

440 

REMOTE DISPLAY 23 NO ANSWER                 187 

 

NFPA 24HR REMINDER                          

441 

REMOTE DISPLAY 24 NO ANSWER                 188 

 

OPTION MODULE                               

442 

REMOTE DISPLAY 25 NO ANSWER                 189 

 

DRILL ACTIVATED                             

443 

REMOTE DISPLAY 26 NO ANSWER                 190 

 

MAN EVAC RECEIVED                           

444 

REMOTE DISPLAY 27 NO ANSWER                 191 

 

MANUAL MODE ENTERED                         

445 

REMOTE DISPLAY 28 NO ANSWER                 192 

 

POWER SUPPLY CABLE NOT CONNECTED            

446 

REMOTE DISPLAY 29 NO ANSWER                 193 

 

NETWORK INCOMPATIBLE                        

447 

REMOTE DISPLAY 30 NO ANSWER                 194 

 

SYSTEM INITIALIZATION                       

448 

REMOTE DISPLAY 31 NO ANSWER                 195 

 

LINK PROTECTOR PRIMARY STATUS               

449 

REMOTE DISPLAY 32 NO ANSWER                 196 

 

LINK PROTECTOR SECONDARY STATUS             

450 

UDACT NO ANSWER                             

197 

 

LINK PROTECTOR PRIMARY NOT PRESENT          

451 

MASTER BOX NO ANSWER                        

198 

 

EVENT BUFFER 80% FULL                       

452 

DAA NO ANSWER                               

199 

 

EBI STATUS                                  

453 

NO ANSWER                                   

200 

 

SOFTWARE MISMATCH                           

454 

NETWORK FAILURE                             

201 

 

NO POWER SUPPLY INST                        

455 

WORKSTATION FAN FAILURE                     

202 

 

TEST PROGRAM UPDATE                         

456 

UPS FAILURE                                 

203 

 

HISTORY 80% FULL                            

457 

NCM COMM FAILURE                            

204 

 

FLASH IMAGE ERROR                           

458 

NODE COMMUNICATIONS FAILURE                 

205 

 

AMPLIFIER LIMIT                             

459 

POWER SUPPLY COMM FAILURE                   206 

 

AMPLIFIER SUPERVISION                       

460 

LOOP 1-2 COMM FAILURE                       

207 

 

DAA ADDRESS CONFLICT                        

461 

LOOP 3-4 COMM FAILURE                       

208 

 

DEVICE SERVICING REQUIRED                   

462 

LOOP 5-6 COMM FAILURE                       

209 

 

DATABASE INCOMPATIBLE                       

463 

LOOP 7-8 COMM FAILURE                       

210 

 

AUDIO LIBRARY INCOMPATIBLE                  

464 

LOOP 9-10 COMM FAILURE                      

211 

 

DAA DOWNLOAD IN PROGRESS                    

465 

DAP PORT A FAILURE                          

212 

 

PHONE CHANNEL LIMIT EXCEEDED                

466 

DAP PORT B FAILURE                          

213 

 

CPU EXECUTIVE ROUTINE RE-ENTERED            

467 

FIM COMM FAILURE                            

214 

 

CPU RECEIVE QUE OVERFLOW                    

468 

LIM COMM FAILURE                            

215 

 

CPU DATA MESSAGE RECEIVED ERROR             

469 

NIM COMM FAILURE                            

216 

 

CPU LEVEL QUE FULL                          

470 

CATASTROPHIC LCD FAILURE ON DIA             

217 

 

CPU CODE MEMORY CHECKSUM ERROR              

471 

CATASTROPHIC DUART FAILURE ON DIA           

218 

 

CPU MESSAGE TRANSMITTED ERROR               

472 

ISIB SCB RECEIVE FAILURE                    

219 

 

AVPS-24 PROBLEM                             

473 

COMMUNICATION  LINK  FAILURE  IN  PORT 
A        

220 

 

DATABASE INCOMPLETE PLEASE REDOWNLOAD       

474 

COMMUNICATION  LINK  FAILURE  IN  PORT 
B        

221 

 

MPS-24 MONITOR CABLE DISCONNECTED           

475 

LAN COMMUNICATIONS FAILURE                   222 

 

TYPE ID CHANGED. SERVICE REQUIRED           

476 

FAILURE                                     

223 

 

TYPE ID CHANGED. SERVICE REQUIRED           

477 

NETWORK FAIL PORT A                         

224 

 

PROG. CHANGE DET. SERVICE REQUIRED          

478 

NETWORK FAIL PORT B                         

225 

 

LIVE TEST - SIGNAL P                        

479 

CHARGER FAIL                                

226 

 

DIB EXECUTIVE ROUTINE RE-ENTERED            

480 

SELF TEST FAILED                            

227 

 

DIB RECEIVE QUE OVERFLOW                    

481 

WORKSTATION COMM FAIL                       

228 

 

DIB DATA MESSAGE RECEIVED ERROR             

482 

LOOP CONTINUITY TEST FAIL LOOP 1            229 

 

DIB CODE MEMORY CHECKSUM ERROR              

483 

Summary of Contents for FieldServer FS-8700-130

Page 1: ...03 Document Revision 0 FieldServer FS 8700 130 Notifier NCA2 NFS2 3030 Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufactured...

Page 2: ...k you for purchasing the FieldServer Please call us for Technical support of the FieldServer product Contact Information Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Contact number 1...

Page 3: ...r Parameters 12 5 4 1 FieldServer Related Map Descriptor Parameters 12 5 4 2 Driver Related Map Descriptor Parameters 12 5 4 3 Map Descriptor Example Standard example 13 Configuring the FieldServer as...

Page 4: ...cy and timeliness of the stored data is limited to the frequency of update messages that the Notifier Fire Panel issues If a networked panel does not send the CLEARED message for latched points via th...

Page 5: ...s FieldServer FieldServer Part 8917 16 Pigtail for RJ45 Port RJ45 Connection to TB5 Printer Port Notifier NCA2 NFS2 3030 Connect to one of the RS 232 Ports on the FieldServer P1 CTX CRX REF PTX PRX RE...

Page 6: ...dware Connection Tips Hints The FieldServer should preferably be connected to the TB5 Printer port It is theoretically possible to connect to the TB5 CRT port but this has not been fully tested The Pa...

Page 7: ...ta Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format FLOAT BIT UInt16 SInt16 Byte Packed_Byte Swapped_Byte Data_Array_Length Numb...

Page 8: ...ng the FieldServer to receive information from a Notifier Panel 5 1 Panel Status Memory Mapping The primary purpose of this driver is to record the status of devices connected to the Notifier panel by...

Page 9: ...s 1 159 Parameter Addresses For each Node Memory Type Node_Trouble Troubles Faults 1 508 Memory Type Panel Panel Maximum12 Boards and 8 Panel circuits per Board Hardware address memory address Board 1...

Page 10: ...rate CRT Port 4800 9600 19200 38400 57600 Vendor limitation Printer Port 9600 Vendor limitation Parity Specify parity None Vendor limitation Data_Bits Specify data bits 8 Vendor limitation Stop_Bits S...

Page 11: ...ce is connected to the FieldServer P1 P8 Node_Inactivity_Timeout Used to monitor the connection to the panel for inactivity Should there be no response from the panel for the set number of seconds the...

Page 12: ...m One of the Node names specified in Section 5 3 Data_Type Specify memory area type Detector Module Detector_Trouble Module_Trouble Panel Panel_Trouble Bell_Trouble Node_Trouble Address Starting addre...

Page 13: ...NODE2 Panel 1 1056 SMD_N2_PANEL_T DA_N2_PANEL_T 0 Passive NODE2 Panel_Trouble 1 96 SMD_N2_BELL_T DA_N2_BELL_T 0 Passive NODE2 Bell_Trouble 1 4 SMD_N2L01D DA_N2L01D 0 Passive NODE2 1 Detector 1 1749 S...

Page 14: ...FS 8700 130 Notifier NCA2 NFS2 3030 Manual Page 14 of 23 CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2 NFS2 3030 6 SERVER This driver cannot be configured as a Server...

Page 15: ...hronize the FieldServer with the panel connect the running FieldServer and press the System Reset button on the panel All current events will be re sent to the FieldServer The port must be enabled on...

Page 16: ...any action on receiving a SYSTEM RESET Normally when a Node initiates SYSTEM RESET by pressing the RESET button on the Panel the panel sends an individual CLEAR message for every point it clears in it...

Page 17: ...states 1 0 SUPERVISORY CLEARED SUPERVISORY states 1 0 TROUBLE FAULT CLEARED TROUBLE FAULT States counter DISABLED CLEARED DISABLED states 1 0 PREALARM CLEARED PREALARM states 1 0 ACTIVE CLEARED ACTIVE...

Page 18: ...OARD 7 278 STYLE 6 POS LOOP 2 25 COMM FAULT LOOP INTERFACE BOARD 8 279 STYLE 6 POS LOOP 3 26 COMM FAULT LOOP INTERFACE BOARD 9 280 STYLE 6 POS LOOP 4 27 COMM FAULT LOOP INTERFACE BOARD 10 281 STYLE 6...

Page 19: ...MANY DEVICES ON LOOP 3 338 REMOTE DISPLAY 5 TROUBLE 85 TOO MANY DEVICES ON LOOP 4 339 REMOTE DISPLAY 6 TROUBLE 86 TOO MANY DEVICES ON LOOP 5 340 REMOTE DISPLAY 7 TROUBLE 87 TOO MANY DEVICES ON LOOP 6...

Page 20: ...ATION ERROR 394 ANNUN 9 NO ANSWER 141 LIB 1 NIB M S PROGRAMMING ERROR 395 ANNUN 10 NO ANSWER 142 LIB 2 NIB M S PROGRAMMING ERROR 396 ANNUN 11 NO ANSWER 143 LIB 3 NIB M S PROGRAMMING ERROR 397 ANNUN 12...

Page 21: ...CTOR PRIMARY NOT PRESENT 451 MASTER BOX NO ANSWER 198 EVENT BUFFER 80 FULL 452 DAA NO ANSWER 199 EBI STATUS 453 NO ANSWER 200 SOFTWARE MISMATCH 454 NETWORK FAILURE 201 NO POWER SUPPLY INST 455 WORKSTA...

Page 22: ...C POWER LOSS BACK UP ACTIVATED 499 STYLE 4 SHORT B L1 246 BUZZER OFF LINE 500 STYLE 4 SHORT A L2 247 PANEL DOOR OPEN 501 STYLE 4 SHORT B L2 248 OFF NETWORK 502 STYLE 4 SHORT A L3 249 INSTALL ERROR 503...

Page 23: ...2 or a corrupted message If this error occurs continuously and you need this new trouble status contact FieldServer 5 Err Unknown OFF NETWORK Node s The FieldServer received a message that a Node eit...

Reviews: