background image

 

FS-8700-130 Notifier NCA2-NFS2-3030 Manual 

Page 18 of 23 

Appendix C.2. System Trouble Messages 

The following table lists the system troubles theoretically recognized by this driver 

– only a selection have 

been tested. 

System Trouble         

Address 

 

System Trouble         

Address 

GROUND FAULT LOOP 1                         

 

STYLE 4 SHORT A L6                          

255 

GROUND FAULT LOOP 2                         

 

STYLE 4 SHORT B L6                          

256 

GROUND FAULT LOOP 3                         

 

STYLE 4 SHORT A L7                          

257 

GROUND FAULT LOOP 4                         

 

STYLE 4 SHORT B L7                          

258 

GROUND FAULT LOOP 5                         

 

STYLE 4 SHORT A L8                          

259 

GROUND FAULT LOOP 6                         

 

STYLE 4 SHORT B L8                          

260 

GROUND FAULT LOOP 7                         

 

STYLE 4 SHORT A L9                          

261 

GROUND FAULT LOOP 8                         

 

STYLE 4 SHORT B L9                          

262 

GROUND FAULT LOOP 9                         

 

STYLE 4 SHORT A L10                         

263 

GROUND FAULT LOOP 10                        

10 

 

STYLE 4 SHORT B L10                         

264 

GROUND FAULT PORT A                         

11 

 

GENERAL PS FAULT                            

265 

GROUND FAULT PORT B                         

12 

 

INSTALLATION ERROR OR CPU/AVPS-24 FAULT      266 

GROUND FAULT                                

13 

 

INSTALLATION ERROR OR CPU/AVPS-24 FAULT      267 

STYLE 6 NEG LOOP 1                          

14 

 

INSTALLATION ERROR OR CPU/AVPS-24 FAULT      268 

STYLE 6 NEG LOOP 2                          

15 

 

EARTH FAULT DETECTED IN WIRING OR SYSTE      269 

STYLE 6 NEG LOOP 3                          

16 

 

EARTH FAULT DETECTED IN WIRING OR SYSTE      270 

STYLE 6 NEG LOOP 4                          

17 

 

EARTH FAULT DETECTED IN WIRING OR SYSTE      271 

STYLE 6 NEG LOOP 5                          

18 

 

COMM FAULT LOOP INTERFACE BOARD 1           

272 

STYLE 6 NEG LOOP 6                          

19 

 

COMM FAULT LOOP INTERFACE BOARD 2           

273 

STYLE 6 NEG LOOP 7                          

20 

 

COMM FAULT LOOP INTERFACE BOARD 3           

274 

STYLE 6 NEG LOOP 8                          

21 

 

COMM FAULT LOOP INTERFACE BOARD 4           

275 

STYLE 6 NEG LOOP 9                          

22 

 

COMM FAULT LOOP INTERFACE BOARD 5           

276 

STYLE 6 NEG LOOP 10                         

23 

 

COMM FAULT LOOP INTERFACE BOARD 6           

277 

STYLE 6 POS LOOP 1                          

24 

 

COMM FAULT LOOP INTERFACE BOARD 7           

278 

STYLE 6 POS LOOP 2                          

25 

 

COMM FAULT LOOP INTERFACE BOARD 8           

279 

STYLE 6 POS LOOP 3                          

26 

 

COMM FAULT LOOP INTERFACE BOARD 9           

280 

STYLE 6 POS LOOP 4                          

27 

 

COMM FAULT LOOP INTERFACE BOARD 10          

281 

STYLE 6 POS LOOP 5                          

28 

 

CATASTROPHIC ISIB COMMUNICATIONS FAULT       282 

STYLE 6 POS LOOP 6                          

29 

 

MEMORY PATTERN FAULT. SERVICE REQUIRED       283 

STYLE 6 POS LOOP 7                          

30 

 

CATASTROPHIC CPU BOARD COMM FAULT           

284 

STYLE 6 POS LOOP 8                          

31 

 

UPLOAD/DOWNLOAD COMMUNICATIONS FAULT        285 

STYLE 6 POS LOOP 9                          

32 

 

STYLE \6\" WIRING OR LOOP #1 ABNORMAL"      

286 

STYLE 6 POS LOOP 10                         

33 

 

STYLE \4\" WIRING OR LOOP #1 ABNORMAL"      

287 

STYLE 6 SHORT L1                            

34 

 

STYLE \6\" WIRING OR LOOP #2 ABNORMAL"      

288 

STYLE 6 SHORT L2                            

35 

 

STYLE \4\" WIRING OR LOOP #2 ABNORMAL"      

289 

STYLE 6 SHORT L3                            

36 

 

STYLE \6\" WIRING OR LOOP #3 ABNORMAL"      

290 

STYLE 6 SHORT L4                            

37 

 

STYLE \4\" WIRING OR LOOP #3 ABNORMAL"      

291 

STYLE 6 SHORT L5                            

38 

 

STYLE \6\" WIRING OR LOOP #4 ABNORMAL"      

292 

STYLE 6 SHORT L6                            

39 

 

STYLE \4\" WIRING OR LOOP #4 ABNORMAL"      

293 

STYLE 6 SHORT L7                            

40 

 

STYLE \6\" WIRING OR LOOP #5 ABNORMAL"      

294 

STYLE 6 SHORT L8                            

41 

 

STYLE \4\" WIRING OR LOOP #5 ABNORMAL"      

295 

STYLE 6 SHORT L9                            

42 

 

STYLE \6\" WIRING OR LOOP #6 ABNORMAL"      

296 

STYLE 6 SHORT L10                           

43 

 

STYLE \4\" WIRING OR LOOP #6 ABNORMAL"      

297 

STYLE 6 RING 1                              

44 

 

STYLE \6\" WIRING OR LOOP #7 ABNORMAL"      

298 

STYLE 6 ON LOOP 1                           

45 

 

STYLE \4\" WIRING OR LOOP #7 ABNORMAL"      

299 

STYLE 6 ON LOOP 2                           

46 

 

STYLE \6\" WIRING OR LOOP #8 ABNORMAL"      

300 

STYLE 6 ON LOOP 3                           

47 

 

STYLE \4\" WIRING OR LOOP #8 ABNORMAL"      

301 

STYLE 6                                     

48 

 

STYLE \6\" WIRING OR LOOP #9 ABNORMAL"      

302 

ANNUN 1 TROUBLE                             

49 

 

STYLE \4\" WIRING OR LOOP #9 ABNORMAL"      

303 

ANNUN 2 TROUBLE                             

50 

 

STYLE \6\" WIRING OR LOOP #10 ABNORMAL"     

304 

ANNUN 3 TROUBLE                             

51 

 

STYLE \4\" WIRING OR LOOP #10 ABNORMAL"     

305 

ANNUN 4 TROUBLE                             

52 

 

UNPROGRAMMED DEVICE ON LOOP 1               

306 

ANNUN 5 TROUBLE                             

53 

 

UNPROGRAMMED DEVICE ON LOOP 2               

307 

ANNUN 6 TROUBLE                             

54 

 

UNPROGRAMMED DEVICE ON LOOP 3               

308 

Summary of Contents for FieldServer FS-8700-130

Page 1: ...03 Document Revision 0 FieldServer FS 8700 130 Notifier NCA2 NFS2 3030 Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufactured...

Page 2: ...k you for purchasing the FieldServer Please call us for Technical support of the FieldServer product Contact Information Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Contact number 1...

Page 3: ...r Parameters 12 5 4 1 FieldServer Related Map Descriptor Parameters 12 5 4 2 Driver Related Map Descriptor Parameters 12 5 4 3 Map Descriptor Example Standard example 13 Configuring the FieldServer as...

Page 4: ...cy and timeliness of the stored data is limited to the frequency of update messages that the Notifier Fire Panel issues If a networked panel does not send the CLEARED message for latched points via th...

Page 5: ...s FieldServer FieldServer Part 8917 16 Pigtail for RJ45 Port RJ45 Connection to TB5 Printer Port Notifier NCA2 NFS2 3030 Connect to one of the RS 232 Ports on the FieldServer P1 CTX CRX REF PTX PRX RE...

Page 6: ...dware Connection Tips Hints The FieldServer should preferably be connected to the TB5 Printer port It is theoretically possible to connect to the TB5 CRT port but this has not been fully tested The Pa...

Page 7: ...ta Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format FLOAT BIT UInt16 SInt16 Byte Packed_Byte Swapped_Byte Data_Array_Length Numb...

Page 8: ...ng the FieldServer to receive information from a Notifier Panel 5 1 Panel Status Memory Mapping The primary purpose of this driver is to record the status of devices connected to the Notifier panel by...

Page 9: ...s 1 159 Parameter Addresses For each Node Memory Type Node_Trouble Troubles Faults 1 508 Memory Type Panel Panel Maximum12 Boards and 8 Panel circuits per Board Hardware address memory address Board 1...

Page 10: ...rate CRT Port 4800 9600 19200 38400 57600 Vendor limitation Printer Port 9600 Vendor limitation Parity Specify parity None Vendor limitation Data_Bits Specify data bits 8 Vendor limitation Stop_Bits S...

Page 11: ...ce is connected to the FieldServer P1 P8 Node_Inactivity_Timeout Used to monitor the connection to the panel for inactivity Should there be no response from the panel for the set number of seconds the...

Page 12: ...m One of the Node names specified in Section 5 3 Data_Type Specify memory area type Detector Module Detector_Trouble Module_Trouble Panel Panel_Trouble Bell_Trouble Node_Trouble Address Starting addre...

Page 13: ...NODE2 Panel 1 1056 SMD_N2_PANEL_T DA_N2_PANEL_T 0 Passive NODE2 Panel_Trouble 1 96 SMD_N2_BELL_T DA_N2_BELL_T 0 Passive NODE2 Bell_Trouble 1 4 SMD_N2L01D DA_N2L01D 0 Passive NODE2 1 Detector 1 1749 S...

Page 14: ...FS 8700 130 Notifier NCA2 NFS2 3030 Manual Page 14 of 23 CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2 NFS2 3030 6 SERVER This driver cannot be configured as a Server...

Page 15: ...hronize the FieldServer with the panel connect the running FieldServer and press the System Reset button on the panel All current events will be re sent to the FieldServer The port must be enabled on...

Page 16: ...any action on receiving a SYSTEM RESET Normally when a Node initiates SYSTEM RESET by pressing the RESET button on the Panel the panel sends an individual CLEAR message for every point it clears in it...

Page 17: ...states 1 0 SUPERVISORY CLEARED SUPERVISORY states 1 0 TROUBLE FAULT CLEARED TROUBLE FAULT States counter DISABLED CLEARED DISABLED states 1 0 PREALARM CLEARED PREALARM states 1 0 ACTIVE CLEARED ACTIVE...

Page 18: ...OARD 7 278 STYLE 6 POS LOOP 2 25 COMM FAULT LOOP INTERFACE BOARD 8 279 STYLE 6 POS LOOP 3 26 COMM FAULT LOOP INTERFACE BOARD 9 280 STYLE 6 POS LOOP 4 27 COMM FAULT LOOP INTERFACE BOARD 10 281 STYLE 6...

Page 19: ...MANY DEVICES ON LOOP 3 338 REMOTE DISPLAY 5 TROUBLE 85 TOO MANY DEVICES ON LOOP 4 339 REMOTE DISPLAY 6 TROUBLE 86 TOO MANY DEVICES ON LOOP 5 340 REMOTE DISPLAY 7 TROUBLE 87 TOO MANY DEVICES ON LOOP 6...

Page 20: ...ATION ERROR 394 ANNUN 9 NO ANSWER 141 LIB 1 NIB M S PROGRAMMING ERROR 395 ANNUN 10 NO ANSWER 142 LIB 2 NIB M S PROGRAMMING ERROR 396 ANNUN 11 NO ANSWER 143 LIB 3 NIB M S PROGRAMMING ERROR 397 ANNUN 12...

Page 21: ...CTOR PRIMARY NOT PRESENT 451 MASTER BOX NO ANSWER 198 EVENT BUFFER 80 FULL 452 DAA NO ANSWER 199 EBI STATUS 453 NO ANSWER 200 SOFTWARE MISMATCH 454 NETWORK FAILURE 201 NO POWER SUPPLY INST 455 WORKSTA...

Page 22: ...C POWER LOSS BACK UP ACTIVATED 499 STYLE 4 SHORT B L1 246 BUZZER OFF LINE 500 STYLE 4 SHORT A L2 247 PANEL DOOR OPEN 501 STYLE 4 SHORT B L2 248 OFF NETWORK 502 STYLE 4 SHORT A L3 249 INSTALL ERROR 503...

Page 23: ...2 or a corrupted message If this error occurs continuously and you need this new trouble status contact FieldServer 5 Err Unknown OFF NETWORK Node s The FieldServer received a message that a Node eit...