-88-
No.EX
※※
-OMZ0016
Item
Resister
area
Bit
No.
Content of diagnostics
Diagnosed area and
processing upon error
How to
reset
Reset conditions
Remarks
(LED indications,
etc.)
Item
Details
Effective
diagnostic
coverage
I/O
processing
upon
diagnosis
System
diagnosis
4
RWr2
8
Number of
system
inputs/outputs
setting error
The number of
occupied system
inputs/outputs has
exceeded the set
value.
System
Continue
Manual
reset
Change the user set
value. Or, adjust the unit
configuration so that the
number of occupied
points is within the set
value.
Base
MS: Flashes red
9
Number of
registered
Remotes
setting error
(Outside of the
wireless
channel setting
range)
More wireless
channels than
specified in the
number of registered
Remotes setting are
registered.
System
Continue
Manual
reset
Change the set value of
the number of registered
Remotes. Or, delete the
registered Remotes
(wireless channels)
outside of the set range.
Base
MS: Flashes red
10 Reserved
-
-
-
-
-
-
11 Reserved
-
-
-
-
-
-
12
Network setting
error
Upper
communication is not
established
System
Stop (HOLD)
Manual
reset
Set the station number
correctly.
Base
MS: Flashes red
or
L ERR: Lights up
red
13 Reserved
-
-
-
-
-
-
14
Wireless
registration
data corrupted
An error has
occurred in the
wireless registration
information.
System
Stop (HOLD)
Manual
reset
Supply power again. If
the error persists after
resupplying power,
contact your SMC sales
representative.
Base
MS: Lights up red
or
W-NS: Lights up
red
15
Detection of
wireless
hardware error
An unrecoverable
error has occurred in
the hardware of the
wireless units.
System
Stop (HOLD)
Manual
reset
Supply power again. If
the error persists after
resupplying power,
contact your SMC sales
representative.
Base
MS: Lights up red
or
W-NS: Lights up
red