(1) Module Input size
In the case of EXW1-RD*, the number is fixed at 16 (16 bits).
* Although the number of occupied inputs of EXW1-RDM* is fixed at 16 (16 bits), only the lower 8 bits
are available.
(2) Module output size
In the case of EXW1-RD*, the number is fixed at 16 (16 bits).
* Although the number of occupied outputs of EXW1-RDM* is fixed at 16 (16 bits), only the lower 8
bits are available.
(3) Wireless communication
If it is set to "Idle", the wireless communication is disconnected.
(4) Detection of a drop in the US1 (for control / input) power voltage
If it is set to "Enable", a drop in the US1 (for control / input) power supply voltage can be detected.
(5) Detection of a drop in the US2 (for output) power voltage
If it is set to "Enable", a drop in the US2 (for output) power supply voltage can be detected.
(6) Output while upper communication is not established
Specify an output action for when the fieldbus communication is disconnected.
CLEAR: Clear the output.
HOLD: Fix the output at the current value.
Individual: Each output setting can be specified.
CLEAR, HOLD, SET: Output ON
(7) Output while wireless communication is not established
Specify an output action for when the wireless communication is disconnected.
CLEAR: Clear all Remote output.
HOLD : Fix all the Remote output at the current value.