![SMC Networks EXW1-BMJA Series Operation Manual Download Page 48](http://html1.mh-extra.com/html/smc-networks/exw1-bmja-series/exw1-bmja-series_operation-manual_1299837048.webp)
-48-
No.EX
※※
-OMZ0016
(6) Error Code
The error code is displayed.
The table below shows error codes and corresponding details and diagnostics maps.
Error Code
Description
Diagnostics map
Item
Bit No.
1
Detection of a short circuit of US1 or
US2
System
diagnostic 1
6 or 7
2
Detection of the range upper limit
3
3
Detection of the range lower limit
2
6
Detection of unconnected load
5
7
User setting upper limit detection
1
8
User setting lower level detection
0
9
Detection of the upper limit of the
ON/OFF cycles
4
16
Detection of US1 power supply
voltage drop
System
diagnosis 2
9
17
Detection of US2 power supply
voltage drop
8
19
Connection failure between units
(during operation)
11
20
Connection failure between units
(when power is supplied)
12
22
Detection of system error (when
power is supplied)
14
23
Detection of hardware error (during
operation)
15
64
Abnormal number of input / output
points setting error
System
diagnosis 3
0
70
Detection of system error
6
71
Detection of hardware error
7
72
Number of system input / output points
setting error
System
diagnosis 4
8
73
Number of registered Remotes setting
error
(Outside of the wireless channel
setting range)
9
76
Network setting error
12
78
Wireless registration data corrupted
14
79
Detection of wireless hardware error
15