-42-
No.EX
※※
-OMZ0016
System setting
Change parameter settings as required.
System setting parameters
Classification
Parameter
Set value
Initial
value
Note
System
Setting
(1)
I/O mapping
Fixed mapping
Fixed
mapping
(2)
Diagnostic mapping
Details
Details
(3)
Analog output update time*1
0.1/0.2/0.5/1/2/5/10/30/60 s
1 s
(4)
Output while upper
communication is not
established
Clear/Hold/Individual
Clear
Output action setting
for when the upper
communication is abnormal
(5)
Wireless communication
timeout
20/40/100/200/500/1,000/
2,000/5,000 msec
500 msec
Activated only when protocol
V.2.0 is used
(6)
Input information while
wireless communication is not
established
Clear/Hold
Hold
Input information
when the wireless
communication is
disconnected
(7)
Wireless communication
Active/Idle
Active
(8)
Protocol
V.1.0/V.2.0
V.1.0
(9)
Time information
-
-
(10)
Time synchronization
-
-
*1: It is necessary to set the data update time for each analog input unit connected to the wireless
Remote.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
•The protocol version is set to V.1.0 by default; to use the 1 Mbps wireless communication
speed and the frequency channel select function (F.C.S.) in a wireless system consisting
solely of EXW1 series devices, change the protocol version to V.2.0 before pairing them.