SI unit parameters
Setting method
No
Parameter
(EDS parameter)
Setting value Contents
Setting
level
Default
setting
By PLC By HT
Enable
Enable monitoring of power
supply voltage for control and
input.
O
1
Power supply voltage
for control and input
monitor
(Pwr control monitor)
Disable
Disable monitoring of power
supply voltage for control and
input.
Unit
O O
Enable
Enable monitoring of power
supply voltage for output
O
2
Power supply voltage
for output monitor
(Pwr output monitor)
Disable
Disable monitoring of power
supply voltage for output
Unit
O O
Enable
Enable valve short circuit
detection
O
3
Short circuit detection
(Monitor short circuit)
Disable
Disable valve short circuit
detection
Unit
O O
Auto
After short circuit has been
removed, the error will be cleared
automatically.
O
4
Restart after short
circuit (Restart after
short circuit)
Manual
After short circuit has been
removed, the error will not be
cleared until the power supply is
reset.
Unit
O O
Enable
Enable valve open circuit
detection
5
Open circuit
Detection
(OC_Mon)
Disable
Disable valve open circuit
detection
Channel
O
X O
Clear
During communication fault, clear
valve output.
O
Hold
During communication fault, hold
valve output.
6
Output setting during
communication fault.
(Fault_MD )
ForceOn
During communication fault, turn
ON valve output.
Channel
X O
Clear
During communication idle, clear
valve output.
O
Hold
During communication idle, hold
valve output.
7
Output setting during
communication idle
(Idle_MD)
ForceOn
During communication idle, turn
ON valve output.
Channel
X O
Enable
If valve’s ON/OFF counter
exceeds the set value, a
diagnostic error will be generated.
Disable
Diagnostic error will not be
generated
O
8
Valve ON/OFF
counter
(Counter)
Val
Set maximum counter value.
Settable values are
(1 ~ 65000) x 1000 times
Channel
65000
X O