- 18 -
No.EX##-OML0007
Baud rate switch: Switches to set the baud rate of internal communication.
Setting 1
No. 3
No. 4
Description
OFF
OFF
1 Mbps (factory setting)
OFF ON
500
kbps
ON OFF
250
kbps
ON ON
125
kbps
Note) 500, 250 & 125 kbps settings are for future extension. Please use 1 Mbps (factory default setting).
Setting 2 switch
The switch settings become effective when power is applied to the unit.
Diagnostics switches: Mapping of diagnostic data to input data
Setting 2
No.1
No.2
Mode
Description
Status size to be set to the
input
OFF
OFF
0
Input data only (factory setting)
0 byte
OFF
ON
1
Input data + system diagnostics
4 byte
ON OFF 2
Input data + system diagn
unit diagnostics (max. 10 units)
6 byte
ON ON
3
Note)
Input data + system diagn
unit diagnostics (max. 64 units)
12 byte
Note) Mode 3 is not currently used; it is for increased functionality in the future.
HOLD/CLR switch
When a fieldbus communication error occurs or when communication stops, all output can be set to Hold
or Clear.
Set the status of this switch in parameters. (Refer to “Parameter settings”)
Setting 2
No.3
Description
OFF
All outputs are cleared when a communication error occurs or during idling. (Factory setting)
ON
All outputs are held when a communication error occurs
Setting 1 Address Data rate
Setting 2