-18-
No.EX##-OME0015-C
•
Output condition setting during I/O connection time-out
1) The instant attribute value below is set to 1 via the network.
Class
Instance
Attribute
Description
Value
0: Switch No.9 setting valid
(Default)
64h
(SMC)
01h 68h
(104)
Hold Clear
(Connection Delete)
1: Fault action valid
or
Class
Instance
Attribute
Description
Value
0: Switch No.9 setting valid
0Fh
(Parameter)
05h 01h
Hold Clear
(Connection Delete)
1: Fault action valid
2) Set the fault action and fault values via the network.
Fault setting method is the individual setting per output with DOP object.
Fault setting
Class
Instance
Attribute
Value
Fault
action
05h
0: Fault set value
1: Output held
Fault
value
09h
(DOP)
n
(Output 1)
06h
0: CLEAR
1: SET
∗:
For details, refer to "Object mounting".
•
Output condition setting when I/O connection is deleted
1) The instant attribute value is set to 1 via the network as indicated below.
Class
Instance
Attribute
Description
Value
0: Follow the setting of ID104
(Default)
64h
(SMC)
01h (01)
69h (105)
Hold Clear
(Connection Delete)
1: CLEAR
2) Set the fault action and fault values via the network.
Fault setting method is the individual setting per output with DOP object.
Fault setting
Class
Instance
Attribute
Value
Fault
action
05h
0: Fault set value
1: Output held
Fault
value
09h (DOP)
n
(Output 1)
06h
0: CLEAR
1: SET
∗:
For details, refer to "Object mounting".