Settings via network (EX12
∗
-SDN1, EX12
∗
-SDN1-X2)
It is possible to set the output operation via the network, when a communication error is generated, in
accordance with the procedure below.
•
Output operation setting at the time of communication error
1) The instant attribute value below is set to 1 via the network
Class
Instance
Attribute
Description
Value
0: Clear setting valid
(Default)
64h
(SMC)
01h
68h (104)
Hold Clear (Timeout)
1: Fault action valid
or
Class
Instance
attribute
Description
Value
0: Clear setting valid
0Fh
(Parameter)
05h
01h
Hold Clear (Timeout)
1: Fault action valid
2) Set the fault action and fault values via the network.
Fault setting method is the individual setting per output with DOP object.
Fault setting
Class
Instance
Attribute
Value
Fault
action
05h
0: Fault set value
1: Output held
Fault
value
09h (DOP)
n
(Output
1)
06h
0: CLEAR
1: SET
∗
: For details, refer to "Object mounting".
•
Output condition setting when I/O connection is deleted
1) The instant attribute value below is set to 1 via the network.
Class
Instance
attribute
Description
Value
0: Follow the setting of
ID104 (Default)
64h
(SMC)
01h (01)
69h (105)
Hold Clear
(Connection Delete)
1: CLEAR
2) Set the fault action and fault values via the network.
Fault setting method is the individual setting per output with DOP object.
Fault setting
Class
Instance
Attribute
Value
Fault
action
05h
0: Fault set value
1: Output held
Fault
value
09h (DOP)
n
(Output
1)
06h
0: CLEAR
1: SET
∗
: For details, refer to "Object mounting".