2 Specifications

3 How to Order

4 Installation

Basic specifications

Rated voltage

24VDC

Range of power
supply voltage

Power supply for input and controlling GW/SI :
24VDC

10%

Power supply for output : 24VDC+10%/-5% ( Voltage
drop warning at around 20V )

Rated current

Power supply for input and controlling GW/SI : 3.0A

@

Inside GW unit : 0.2A

@

Input device and SI control section : 2.8A

Power supply for solenoid valves and output : 3A

Number of input/
output points

Input point : Max. 64/Output point : Max. 64

(

)

Higher-level bus

Protocol

Media

Max. segment length

Max. transceiver number

Communication method

Fieldbus protocol

Ethernet (IEEE802.3)

Port No.

IP address setting range

192.168.0.1 to 192.168.0.254 ( Setting by an
internal switch )
Or optional setting by the DHCP server

Device information

Vendor ID

: 7 ( SMC Corp. )

Product type : 12 ( communication adapter )
Product code : 104

Communication
speed

I/O message

100BASE-TX

10M/100Mbps

(Automatic selection or manual setting)

100m (328ft)

2 (per segment)

Full duplex/Half duplex
(automatic selection or manual setting)

EtherNet/IP

TM

Release1.0

Input

: 16 byte ( assembly instance : 100 )

Output : 16 byte ( assembly instance : 150 )

44818 (0xAF12)

EX500

GEN1

Communication protocol

EN1

EtherNet/IP

Cutout Dimensions for Mounting ( Tolerance :    0.2 )

148

6

8

5

4 M5

Tightening torque : 

 (1.5   0.2) N  m

Thread mounting

EX500-TFK41GB-A

Installation & Maintenance Manual

EtherNet/IP

TM

Compatible GW Unit

Type EX500-GEN1

1 Safety Instructions

If instructions are not followed there is a possibility of

serious injury or loss of life.

If instructions are not followed there is a possibility of
injury or equipment damage.

1 Safety Instructions (continued)

WARNING

CAUTION

• This manual contains essential information for the protection of users

and others from possible injury and/or equipment damage.

• Read this manual before using the product, to ensure correct handling,

and read the manuals of related apparatus before use.

• Keep this manual in a safe place for future reference.
• These instructions indicate the level of potential hazard by label of

“DANGER”, “WARNING” or “CAUTION”, followed by important safety
information which must be carefully followed.

To ensure safety of personnel and equipment the safety instructions in

this manual and the product catalogue must be observed, along with

other relevant safety practices.

WARNING

CAUTION

Do not disassemble, modify (including change of printed circuit
board) or repair the product.

An injury or product failure may result.

Do not operate the product beyond the specification range.

Fire, malfunction or equipment damage may result. Use the product
only after confirming the specifications.

Do not use the product in the presence of flammable, explosive or

corrosive gas.

Fire, explosion or corrosion may result. This product does not have an
explosion proof construction.

When using the product as part of an interlocking system:

1) Provide a double interlocking system, for example a mechanical

system.

2) Check the product regularly to ensure proper operation.

Before performing maintenance, be sure of the following:

1) Turn off the power supply.
2) Stop the air supply, exhaust the residual pressure and verify the

release of air from the system.

• Always perform a system check after maintenance.

Do not use the product if any error occurs.
Safety cannot be assured if caused by un-intentional malfunction.

• Provide grounding to ensure correct operation and to improve

noise resistance of the product.

This product should be individually grounded using a short cable.

Follow the instructions given below when handling the product.
Failing to do so may result in product damage.

• Maintenance space should always be provided around the product.
• Do not remove labels from the product.
• Do not drop, hit or apply excessive shock to the product.
• Follow all specified tightening torques.

• Do not bend, apply tensile force, or apply force by placing heavy

loads, on the cables.

• Connect wires and cables correctly, and do not connect while the

power is ON.

• Do not route wires and cables together with power or high-voltage

cables.

• Check the insulation of wires and cables.
• Take proper measures against noise, such as noise filters, when the

product is incorporated in equipment or devices.

• Select the required protection (IP) rating according to the environment

of operation.

• Take sufficient shielding measures when the product is to be used in the

following conditions:

(1) where noise due to static electricity is generated.
(2) where electro-magnetic field strength is high.
(3) where radioactivity is present.
(4) where power lines are located.

• Do not use the product in a place where electric surges are generated.
• Use suitable surge protection when a surge generating load such as a

solenoid valve are to be directly driven.

• Prevent any foreign matter from entering this product.
• Do not expose the product to vibration or impact.
• Use the product within the specified ambient temperature range.
• Do not expose the product to any heat radiation.
• Use a precision screwdriver with flat blade to adjust the DIP switch.
• Close the cover over the switches before power is applied.
• Do not clean the product with chemicals such as benzene or thinners.

• Power Supply selection

A UL approved direct current (DC) power supply should be used with this
product, as follows:
1. A limited voltage / current supply in accordance with UL508.

A circuit from which power is supplied by the secondary coil of a

transformer according to the following:

Maximum voltage (no load) : Less than 30Vrms (42.4V peak)
Maximum current : (1) Less than 8A (including when short circuited)

(2) Limited by circuit protection (such as a fuse) with the

following rating.

2. A Class 2 power supply unit in accordance with UL1310, or a power

supply circuit of maximum 30Vrms (42.4V peak) or less, using a Class 2
transformer in accordance with UL1585 as power source.

No load voltage (V peak)

0 to 20 [V]

20 to 30 [V]

Max. current (A)

5.0

100 / peak voltage

5 Display / Setting

GATEWAY UNIT

EX500 SERIES

COM A

COM B

COM C

COM D

LAN

NS

MS

100

LINK

PWR

Display

Secure at four positions with screws with head diameter of 5.2 or more and
thread length of 15mm or more.

Display

Contents

PWR

OFF

The power supply for solenoids is insufficient

Green light ON

The power supply for solenoids is normal

LINK

OFF

The power supply is OFF/initialized

Green light ON

Ethernet communication established

Green flashing

Data sent/received

100

OFF

Communication at 10Mbps

Green light ON

Communication at 100Mbps

MS

OFF

The power supply is OFF

Green light ON

Operating normally

Green flashing

Setting error

Red flashing

Recoverable internal error

Red light ON

Unrecoverable internal error

NS

OFF

The power supply is OFF/IP address not set

Green flashing

EtherNet/IP-level communication not
established

Green light ON

Multiple EtherNet/IP-level
communications established

Red flashing

Multiple EtherNet/IP-level
communications time out

Red light ON

IP address duplicated

COM A

OFF

No input data

Green light ON

Input data received

COM B

OFF

No input data

Green light ON

Input data received

COM C

OFF

No input data

Green light ON

Input data received

COM D

OFF

No input data

Green light ON

Input data received

NOTE

When connecting manifold valve only without connecting Input unit manifold,

LEDs of COM A to D do not light. To make them light, connect a terminal plug to

the unused connector of SI unit ( "C1" or "0" ).