ClimateWorx ProtoNode Start-up Guide
Page 9 of 46
3.3 Configuring Device Communications
3.3.1 Input COM Settings on all Devices Connected to the ProtoNode
All of the connected serial devices
MUST have the same Baud Rate, Data Bits, Stop Bits,
and Parity settings as the ProtoNode.
specifies the device serial port settings required to communicate with the ProtoNode.
Port Setting
Device
Protocol
Modbus RTU
Baud Rate
9600
Parity
None
Data Bits
8
Stop Bits
1
Figure 4: COM Settings
3.3.2 Set Modbus Node-ID for each Device attached to the ProtoNode
Set Modbus Node-ID for each of the devices attached to ProtoNode. The Modbus Node-
ID’s
need to be uniquely assigned between 1 and 255.
o
The Modbus Node-ID that is assigned for each device needs to be documented
The Modbus Node-
ID’s assigned are used for designating the Device Instance
for BACnet/IP and BACnet MS/TP (
The Metasys N2 and Modbus TCP/IP field protocol Node-IDs are automatically set to be the
same value as the Node-ID of the Modbus RTU device.