ClimateWorx ProtoNode Start-up Guide
Page 41 of 46
Compressor 1 Overload Alarm
BI 12
x x x x
Comp.1 Overload
BI 12 DI 12 nvoComp1Over_XXX
SNVT_switch
10012
Compressor 2 High Pressure
BI 13
d d d d
Comp.2 H pressure
BI 13 DI 13 nvoComp2HPrs_XXX
SNVT_switch
10013
Compressor 2 Low Pressure Alarm
BI 14
d d d d
Comp.2 L pressure
BI 14 DI 14 nvoComp2LPrs_XXX
SNVT_switch
10014
Compressor 2 Overload Alarm
BI 15
d d d d
Comp.2 Overload
BI 15 DI 15 nvoComp2Over_XXX
SNVT_switch
10015
High Return Temperature Alarm
BI 16 x x x x x
High R.Temp
BI 16 DI 16 nvoHiRTmp_XXX
SNVT_switch
10016
Low Return Temperature Alarm
BI 17 x x x x x
Low R.Temp
BI 17 DI 17 nvoLoRTmp_XXX
SNVT_switch
10017
High Return Humidity Alarm
BI 18 x x x x x
High R.Humidity
BI 18 DI 18 nvoHiRHum_XXX
SNVT_switch
10018
Loss of Return Air Sensor
BI 19 x x x x x
Low R.Humidity
BI 19 DI 19 nvoLoRHum_XXX
SNVT_switch
10019
High Supply Temperature Alarm
BI 20 o o o o o
Lose of R.Sensor
BI 20 DI 20 nvoLossofRSn_XXX
SNVT_switch
10020
High Supply Air Temp
BI 21 o o o o o
High S.Temp
BI 21 DI 21 nvoHiSTmp_XXX
SNVT_switch
10021
Low Supply AirTemp
BI 22 o o o o o
Low S.Temp
BI 22 DI 22 nvoLoSTmp_XXX
SNVT_switch
10022
High Supply Air Humidity
BI 23 o o o o o
High S.Humidity
BI 23 DI 23 nvoHiSHum_XXX
SNVT_switch
10023
Low Supply Air Humidity
BI 24 o o o o o
Low S.Humidity
BI 24 DI 24 nvoLoSHum_XXX
SNVT_switch
10024
Lose of Supply Air Sensor
BI 25 o o o o o
Lose of S.Sensor
BI 25 DI 25 nvoLossofSSn_XXX
SNVT_switch
10025
High voltage
BI 26 x x x x x
High voltage
BI 26 DI 26 nvoHiVolt_XXX
SNVT_switch
10026
Low voltage
BI 27 x x x x x
Low voltage
BI 27 DI 27 nvoLoVolt_XXX
SNVT_switch
10027
Custom Fault 1
BI 28 x x x x x
Custom Fault 1
BI 28 DI 28 nvoCustmFlt1_XXX
SNVT_switch
10028
Custom Fault 2
BI 29 x x x x x
Custom Fault 2
BI 29 DI 29 nvoCustmFlt2_XXX
SNVT_switch
10029
Lose of Comp.EX1
BI 30
x x x x
Lose of Comp.EX1
BI 30 DI 30 nvoLosCmpEx1_XXX
SNVT_switch
10030
Lose of Comp.EX2
BI 31
d d d d
High S.Temp
BI 31 DI 31 nvoHiSTmp_XXX
SNVT_switch
10031
Filter Drier Drity
BI 32
o o o o Requires Filter Drier Sensor Package
Low S.Temp
BI 32 DI 32 nvoLoSTmp_XXX
SNVT_switch
10032
Binary Inputs (Read Write)
Standby enable
BV 1
x x x x x
1
General Alarm
BV 2
x x x x x
2
Critical Alarm
BV 3
x x x x x
3
Fan Motor
BV 4
x x x x x
4
Humidifier
BV 5
o o o o o
5
Reheat Stage 1
BV 6
o o o o o These values require staged reheat
6
Reheat Stage 2
BV 7
o o o o o
7
Reheat Stage 3
BV 8
o o o o o
8
Pump
BV 9
x
x x x
9
Humidifier 25% Output
BV 10 o o o o o
10
SetManualMode
BV 12 x x x x x Sets manual mode
12
On/Off
BV 13 x x x x x Turns Unit On or Off
13
Restore Default Settings
BV 41 x x x x x
41
Restore Default Alarm Settings
BV 42 x x x x x
42