HRX-OM-W058
Chapter 9 Documents
HRS-R Series
9.1
Specifications List
9-1
Chapter 9 Documents
9.1 Specifications List
9.1.1
Product specification
Table 9-1 Specifications List [HRS
-
-20-
-R]
Model
HRS018-A
-20-
-R
HRS030-A
-20-
-R
Cooling method
Air-cooled refrigeration
Refrigerant
R410A (HFC)
Quantity of refrigerant
kg
0.39
Control method
PID control
Ambient temperature and humidity
*1
Temperature: 5 to 45
o
C, Humidity: 30 to 70%,
Ci
rcul
ati
ng fl
ui
d s
y
s
tem
Circulating fluid
*2
Tap water, 15% ethylene glycol aqueous solution
*4
Operating temperature range
*1
o
C
5 to 40
Cooling capacity
*3
(50/60Hz)
W
1700 / 1900
2500 / 2900
Temperature stability
*5
o
C
±0.1
Pump capacity
*6
(50/60Hz)
MPa
0.13(at 7 L/min) / 0.18 (at 7 L/min)
For option -T: 0.35(at 10L/min)/0.35(at 14L/min)
Rated fiow
*7
(50/60Hz)
L/min
7/7
For option -T
:
10/14
Tank capacity
L
Approx. 5
For option -L
:
Approx. 12
Port size
Rc1/2
Rc1/2
Wetted material
Stainless steel, Copper (Heat exchanger brazing), Bronze,
Alumina ceramic
*12
,Carbon, PP, PE, POM, FKM, EPDM, PVC
Auto
mati
c
fl
ui
d
fi
lli
ng
*14
Feed water pressure range
MPa
0.2 to 0.5
Feed water temperature range
o
C
5 to 40
Feed water capacity
L/min
Approx. 1
Automatic fluid filling Port size
Rc 3/8
Over flow port Port size
Rc 3/4
El
ec
tric
s
y
s
tem
Power supply
Single-phase 200 to 230 VAC (50/60 Hz)
Allowable voltage range ±10% (No continuous voltage fluctuation)
Applicable earth leakage breaker capacity
*8
A
10
For option T:15
Rated operating current
*3
(50/60Hz)
A
5.1 / 5.6
For option T:6.2/7.7
5.4 / 6.1
For option T:6.4/7.8
Rated power consumption
*3
(50/60Hz)
kVA
1.0 / 1.1
For option T:1.3/1.6
1.1 / 1.2
For option T:1.4/1.7
IP rating (Electrical BOX)
IP54 (Cable gland:IP67)
Noise level
*9
(50/60Hz)
dB
62 / 65
Dimensions
*10
mm
W377xD500xH615
Accessory
Fitting (for drain outlet) 1 pc.
*13
, Input/output signal connector 1 pc.,
Operation Manual (for installation/operation) 1,
Alarm code list sticker 1, Ferrite core (for communication) 1 pc.,
Power supply cable: to be prepared by user.
Weight
*11
kg
45
*1 Use the product in conditions where freezing will not occur.
Consult with SMC if using in a season or region where the ambient temperature will fall below zero.
*2 If tap water is used, use water which satisfies the standard of The Japan Refregeration And Air Conditioning Industry Association
(JRA GL-02-1994/Cooling water system - circulation type - make-up water)
*3 (1)AC Input: 200VAC, (2)Operating ambient temp.: 25
o
C, (3)Circulating fluid temp.: 20
o
C, (4)Circulating fluid rated flow, (5)Criculating fluid : Tap water
The cooling capacity will be reduced by 300W when option T is selected.
*4 Use a 15% ethylene glycol aqueous solution if operating in a place where the circulating fluid temp. is lower than 10
o
C.
*5 Outlet temp. when the circulating fluid flow is rated flow, and the circulating fluid outlet and the return are directly connected.
Installation environment and power supply are within specification range and stable.
*6 The capacity at the thermo-chiller outlet when the circulating fluid temp. is 20
o
C.
*7 Fluid flow to maintain the cooling capacity and the temperature stability.
The specification of the coolong capacity and the temperature stability may not be satisfied if the flow rate is lower than the rated flow.
*8 To be prepared by the customer. Use an earth leakage breaker with sensitivity of 15mA or 30mA/100V in power supply specification.
*9 Front 1m/Height 1m/Static with no load. See note 3 for other conditions.
*10 Dimension between panels. Projection is not included.
*11 Weight when the circulating fluid is not included.
The weight will increase by 1kg when option J [Automatic fluid filling] is selected.
The weight will increase by 1kg when option L [Large capacity tank] is selected.
The weight will increase by 2kg when option B [Earth leakage breaker] is selected.
The weight will increase by 6kg when option T [High pressure pump] is selected.
*12 In case option T [High pressure pump] selected.
*13 In case option T [High pressure pump] selected, this fitting is not enclosed as accessory.
*14 In case option J [Automatic fluid filling] selected.