HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series
5.16
Alarm customize function
5-45
32.
Select temperature alarm monitoring method from the table below with [▲] key or [▼]
key, and confirm by pressing “SEL”.
Table 5.16-17
List of set value
Set value
Item
Explanation
Initial value
(Default setting)
Continuous
monitoring
Alarm monitoring starts at the same time as it is
turned on.
○
Automatic
monitoring
When the circulating fluid temperature is outside of
the alarm threshold range at the time of operation
start, the alarm will not be generated until the
temperature comes inside the alarm threshold
range.
Monitoring
start timer
Alarm will not be generated until it reaches the time
set for the AS.22 "Monitoring start timer" after the
operation starts.
Alarm monitoring starts when it reaches the set time.
Automatic
monitoring
+
Monitoring
start timer
Alarm will not be generated until it reaches the time
set for the AS.22 "Monitoring start timer" after the
operation starts.
Alarm monitoring starts when it reaches the set time.
When the circulating fluid temperature enters the
alarm threshold range before it reaches the set time,
the alarm monitoring will be started at that time.
Settings of this function and example of alarm generating timing for 5.15.3 "Setting of temperature alarm
monitoring method and generation timing".
Monitoring start timer Setting and Checking
33.
Press the [SEL] key once.
Setting screen of the monitoring start timer is displayed on the digital display.
34.
Select monitoring start timer from the table below with [▲] key or [▼] key, and confirm
by pressing “SEL”.
Table 5.16-18
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are impossible when "0:
Continuous monitoring" or "1: Automatic
monitoring" is selected for the setting of AS21
"Temperature alarm monitoring method".
○
to
Sets the time when alarm monitoring starts
Setting unit is 1 minute.
Settings of this function and example of alarm generating timing for 5.15.3 "Setting of
temperature alarm monitoring method and generation timing".
PV
SV