Rev. 1.2 of 12.2020
31
4.13.
List of Component Modules
The list of modules presented below is optional and depends on the technical conditions at the
installation site and the intended function of the unit assumed by the designer of the system
supplied.
No
.
Module
Application
Overview
1.
MZR
Cooperating two power
sources (main-reserve).
Automatic switching of the power supply to the
reserve with the use of the Automatic Switching
Reserve system.
2.
MZ24
24 V DC power supply
unit with battery
backup.
Various output power options available,
depending on the actual load. Output current for
a single module from 5,5 A to 50 A.
3.
MZSW
Power supply unit for
fire safety fan motors.
Various options of the module are available,
depending on the motor type and its operating
duty:
-
automatic activation or star triangle
-
two-speed or two-way duty
-
two-way and two-speed duty
-
activation and supplying through a frequency
converter
4.
MZKDC
Power supply unit for
the components of the
smoke and heat control
system.
The module ensures uninterruptible power
supply to constituents of systems described by
a series of standards, i.e. PN-EN
12101 “Smoke
and heat control systems”. The module controls
the status of the line safety devices and accuracy
of the power supply. It is manufactured in two
versions
–
for AC and DC power supply.
5.
MZKP
Power supply unit for
the fire damper
actuators.
Changing the fire damper position by applying
voltage to various actuator contacts or by de-
energising the actuator (spring return actuator).
6.
MZOD
Power supply unit for
smoke ventilation door
and window actuators.
The actuator is controlled by changing the
polarisation of the supply voltage. It is possible
to monitor the door and window opening with
a potential-free contact.
7.
MSOA
Power supply unit for
strobe light sirens.
The module may be adapted to 24 V DC or
230 V AC power supply. The module safety
circuits are adjusted according to the power and
number of supplied signalling devices.
8.
MKL
Detection of damage to
power cables supplying
peripheral actuators.
It enables the Control Panel to continuously
supervise the status of the installation supplying
power to consumer equipment.
9.
MMG
Power generator
monitoring.
It is used when a power generator is a backup
power supply. The module makes it possible to
receive the signals indicating the generator
status from the potential-free contacts.
10.
MPP
Overvoltage protection.
It protects the system against the effects of
lightning strikes on the installation and
overvoltages resulting from switching processes
in the electric network.
Summary of Contents for ZUP
Page 6: ...Rev 1 2 of 12 2020 6 2 13 Declaration of Performance ...
Page 7: ...Rev 1 2 of 12 2020 7 ...
Page 8: ...Rev 1 2 of 12 2020 8 ...
Page 43: ...Rev 1 2 of 12 2020 43 Annexes 14 13 ZUP Assembly and On site Launch Instruction Manual ...
Page 44: ...Rev 1 2 of 12 2020 44 ...
Page 45: ...Rev 1 2 of 12 2020 45 ...
Page 46: ...Rev 1 2 of 12 2020 46 ...
Page 47: ...Rev 1 2 of 12 2020 47 ...