background image

 

 

 

 

 

page 6 z 6 

Installation manual WKP type multi-blade fire damper

 

Version: 2.0.1 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

Figure 2. 

Installation method of the WKP type multi-blade fire dampers in concrete or brickwork walls

 

Summary of Contents for WKP

Page 1: ......

Page 2: ...eet steel fig 1 on the inner side of the installation opening 3 Screw previously prepared plasterboards to the fixed sections a With thickness of 12 5 mm and width of 125 mm 8 pcs Two by wto on both sides of the installation opening b With thickness of 12 5 mm and width of 40 mm 3 pcs Directly adjacent to the spacer insulating the body of the device 4 Fill the steel flanges of the fire damper with...

Page 3: ...istance of no more than 25 mm from the clearance of the fire damper see Fig 1 It is prohibited to place the screws within 50 mm from the release of the locking mechanism In order to ensure the access to the electric drive mechanism make an additional opening in the flange made of plasterboards with dimensions of 140x320 mm from the appropriate side of the partition wall 9 Install the mounting fram...

Page 4: ...page 4 z 6 Installation manual WKP type multi blade fire damper Version 2 0 1 Figure 1 Installation method of the WKP type multi blade fire dampers in lightweight partition walls ...

Page 5: ...ed downwards respectively by dimension N x 100 where N the number of blade driven directly by the actuator 3 Put the fire damper into the installation opening in such way that the axis of the fire damper matches the axis of the wall 4 After setting the fire damper fill the gap between the fire damper and the wall with cement mortar lime mortar or concrete 5 Install the mounting frames on both side...

Page 6: ...page 6 z 6 Installation manual WKP type multi blade fire damper Version 2 0 1 Figure 2 Installation method of the WKP type multi blade fire dampers in concrete or brickwork walls ...

Reviews:

Related manuals for WKP