Installation manual WKP type multi-blade fire damper

 

Version: 2.0.1 

 

 

Remarks on WKP-T fire damper 

Screw the last board (thick. 12.5 [mm] and a width of 300 [mm]), which covers the 

lever system side, leading the screws along the length of the section at a distance  

of no more than 25 [mm] from the clearance of the fire damper - (see Fig. 1). It is 

prohibited  to place the screws within 50 [mm]  from the release of the locking 

mechanism. In order to ensure the access to the electric drive mechanism, make an 

additional opening in the flange  made of plasterboards, with dimensions  

of 140x320 [mm] from the appropriate side of the partition wall. 

 

9.

 

Install the mounting frames on both sides of the wall and mount the masking grilles. 

 

 

Summary of Contents for WKP

Page 1: ......

Page 2: ...eet steel fig 1 on the inner side of the installation opening 3 Screw previously prepared plasterboards to the fixed sections a With thickness of 12 5 mm and width of 125 mm 8 pcs Two by wto on both sides of the installation opening b With thickness of 12 5 mm and width of 40 mm 3 pcs Directly adjacent to the spacer insulating the body of the device 4 Fill the steel flanges of the fire damper with...

Page 3: ...istance of no more than 25 mm from the clearance of the fire damper see Fig 1 It is prohibited to place the screws within 50 mm from the release of the locking mechanism In order to ensure the access to the electric drive mechanism make an additional opening in the flange made of plasterboards with dimensions of 140x320 mm from the appropriate side of the partition wall 9 Install the mounting fram...

Page 4: ...page 4 z 6 Installation manual WKP type multi blade fire damper Version 2 0 1 Figure 1 Installation method of the WKP type multi blade fire dampers in lightweight partition walls ...

Page 5: ...ed downwards respectively by dimension N x 100 where N the number of blade driven directly by the actuator 3 Put the fire damper into the installation opening in such way that the axis of the fire damper matches the axis of the wall 4 After setting the fire damper fill the gap between the fire damper and the wall with cement mortar lime mortar or concrete 5 Install the mounting frames on both side...

Page 6: ...page 6 z 6 Installation manual WKP type multi blade fire damper Version 2 0 1 Figure 2 Installation method of the WKP type multi blade fire dampers in concrete or brickwork walls ...

Reviews: