SmartPlug 1Led User Manual Download Page 6

 

Note:

 If this configuration is set to ‘0’, all the functions of “Configuration No. 6, 8, 9, 10, 11” are 

invalid.  And  No  Current,  Voltage,  Active  Power  and  Accumulated  Power  monitored  and  reported 
any more. 

Parameter Number  Size (Byte) 

Available Settings 

Default value 

0, 1 

 

6)

 

Meter Report Enable 
This configuration sets the meter report function enabled or disabled. 
‘0’ – Disable meter report function. 
‘1’ – Enable meter report function with time interval defined by “

Configuration No. 11

”. 

When device is detected an OCP event or the relay turned on or turned off, device still will 
report all meter values once if this value be set to ‘0’. 
Parameter Number  Size (Byte) 

Available Settings 

Default value 

0, 1 

 

7)

 

Countdown Time Setting 
This configuration sets the time length for turning off the device. This configuration is only 
valid when “

Configuration No.4

” is set to ‘1’. Unit: minute. 

Parameter Number  Size (Byte) 

Available Settings   

Default value (min) 

0 ~ 30000 

120 

 

8)

 

Maximum output current setting 
This configuration sets the maximum output current that the device can provide. When the 
current consumed by the load is greater than the setting value, the device will automatically 
cut off the power of the load and send out alarm information, and the led will light on 1.5s 
with 2s interval. Unit: 0.01A (Ampere). 
This value must be great than the alarm value defined by 

Configuration No. 9

Parameter Number 

Size (Byte) 

Available Settings   

Default value 

0 ~ 1600 

1600 

 

9)

 

Output Current Alarm 
This configuration sets the alarm value of the load current (volatility). When the load current 
is large than this value, the led will light on 0.5s with 2s interval. Unit: 0.01A (Ampere). 
This  value  must  be  less  than  the  max.  output  value  defined  by 

Configuration  No.  8

.

Parameter Number  Size (Byte) 

Available Settings 

Default value 

0 ~ 1550 

1500 

 

10)

 

Current Change Ratio 
This configuration sets the changed value of the load current (volatility). When the 
differential between two measurements of current consumed by the load exceeds the value 
set by this configuration, the device will report the last measured results automatically to 
the controller.   
The changed value = [Value] 

×

  0.01A. 

 

Summary of Contents for 1Led

Page 1: ...tPlug 1Led User Manual Z Wave 700s S2 Version Version Written By Date Change List 1 0 Yongqi 20201022 Initial 1 1 Yongqi 20210116 Fixed Some Error Descriptions 1 2 Yongqi 20210304 Add Note for OTA Led...

Page 2: ...f Blue led will blink with 1s interval until inclusion successful Remove 1 Power up the device 2 Set Z Wave Controller into exclusion mode 3 Press and hold the button for 5s until Blue led lights is o...

Page 3: ...CLASS_INDICATOR COMMAND_CLASS_DEVICE_RESET_LOCALLY SWITCH_BINARY_REPORT NOTIFICATION_REPORT METER_REPORT INDICATOR_REPORT DEVICE_RESET_LOCALLY_NOTIFICATION 2 Control COMMAND_CLASS_BASIC BASIC_SET Devi...

Page 4: ...ive energy value 2 Execute the factory reset operation to reset the cumulative energy value The cumulative energy will not be reset if SmartPlug remove from Z Wave Network by exclusion operation Over...

Page 5: ...ize Byte Available Settings Default value 1 1 0 1 1 2 Button Switch Function Disable Setting this configuration as 0 will be disabling to turn on and off the relay by pressed button Parameter Number S...

Page 6: ...nt setting This configuration sets the maximum output current that the device can provide When the current consumed by the load is greater than the setting value the device will automatically cut off...

Page 7: ...itch Set 0 3 Basic Set 1 99 maps to Binary Switch Set 255 4 Basic Get Report maps to Binary Switch Get Report SmartStart SmartStart enabled products can be added into a Z Wave network by scanning the...

Page 8: ...Support Yes No SECURITY_KEY_S0 Yes SECURITY_KEY_S2_UNAUTHENTICATED Yes SECURITY_KEY_S2_AUTHENTICATED Yes SECURITY_KEY_S2_ACCESS No All Supports Command Class in Each NIF Lists Command Class Version N...

Page 9: ...with S0 level COMMAND_CLASS_MANUFACTURER_SPECIFIC is supported non securely And when device is included with S2 level COMMAND_CLASS_MANUFACTURER_SPECIFIC is supported securely only Notice 2 Indicates...

Page 10: ...Z Wave Network Send NIF Blink with 1s Interval Add to Z Wave Network Blink with 300ms Interval OTA is Running Note 1 The LED State is Not Changed when Led Is Busy On or Blink Such as Relay on Over Cu...

Reviews: