MGC100 Petrol Genset Controller User Manual                                                                  Page 10 of 16 

6

 

CONNECTION 

 

Fig.2 Rear Panel 

Table 6 Terminal Connection Description 

No. 

Function 

Cable Size 

Note 

B- 

1.0mm

2

 

Connected with negative of starter battery. 

B+ 

1.0mm

2

 

Connected with negative of starter battery. If wire length 
is over 30m, better to double wires in parallel. Max. 10A 
fuse is recommended. 

Start Relay Output 

1.0mm

2

 

B+ power is supplied by terminal 2, rated 7A. 
Connected with start coil of starter. 

Fuel Relay Output 

1.0mm

2

 

B+ power is supplied by terminal 2, rated 7A. 

Controller Types 

1.0mm

2

 

When this terminal short connected with (B+), it used as 
diesel genset controller. 

When  this  terminal  connected  with  nothing,  it  used  as 

petrol genset controller. 

High Temperature 

1.0mm

2

 

Ground connected is active (B-). 

Low Oil Pressure 

1.0mm

2

 

Ground connected is active (B-). 

Emergency Stop 

1.0mm

2

 

Ground connected is active (B-). 

Remote Start 

1.0mm

2

 

Ground connected is active (B-). 

10 

Aux. Transistor 

1.0mm

2

 

B- power is supplied by terminal 1, rated 1A. 

11 

Magnetic Pickup 2 
(B-)  has  already  connected 

with controller innerly. 

0.5mm

2

 

Connected  with  Rotate  Speed  Sensor,  shielding  line  is 

recommended. 

12 

Magnetic Pickup 1 

0.5mm

2

 

13 

1.0mm

2

 

Connected with N wire. 

14 

W phase voltage monitor 

1.0mm

2

 

Connected with W phase (2A fuse is recommended). 

15 

V phase voltage monitor 

1.0mm

2

 

Connected with V phase (2A fuse is recommended). 

16 

U phase voltage monitor 

1.0mm

2

 

Connected with U phase (2A fuse is recommended). 

 

Summary of Contents for MGC100

Page 1: ...MGC100 PETROL GENSET CONTROLLER USER MANUAL...

Page 2: ...NEL 7 4 2 2 ALARM ICON INDICATION 8 4 2 3 PANEL INDICATOR 8 4 3 OPERATION 8 4 3 1 REMOTE START SEQUENCE 8 4 3 2 REMOTE STOP SEQUENCE 8 4 3 3 MANUAL START STOP 9 5 PROTECTION 9 6 CONNECTION 10 7 DEFINI...

Page 3: ...n permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above Any reference to trademarked product names used within this publication is owned...

Page 4: ...lights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictly observed could result in damage or destruction of equipment WARNING Ind...

Page 5: ...atus Chose to control Petrol Genset or Diesel Genset via connection Suitable for 3 phase 4 wire 3 phase 3 wire 2 phase 3 wire single phase 2 wire 120V 240V systems with frequency 50 60 Hz Protection f...

Page 6: ...AC 360V ph N AC 30V AC 360V ph N AC Frequency 50Hz 60Hz Speed Sensor Voltage 1 0V to 24V effective value Speed Sensor Frequency 10000Hz Max Start Relay 7A DC12V power supply Fuel Relay 7A DC12V power...

Page 7: ...icator are normal In setting menu upturn or decrease parameter value it can be double clicked In setting menu press it for more than 3s to exit this menu Page Confirm Switch display contents of nixie...

Page 8: ...y are disengaged for the pre set rest period Crank Rest Time begins and wait for the next crank attempt after the Crank Rest Time delay start for 3s preheat and ETS start to output after Crank Rest Ti...

Page 9: ...2s 2 High Temperature detect when start Alarm Stop when High Temperature is active and lasts for 2s 3 Over Speed detect when start Alarm Stop after duration exceeds Over Speed Stop Delay 4 Gen Over V...

Page 10: ...enset controller When this terminal connected with nothing it used as petrol genset controller 6 High Temperature 1 0mm2 Ground connected is active B 7 Low Oil Pressure 1 0mm2 Ground connected is acti...

Page 11: ...start the genset P05 Stop Delay 0 3600 s 1 Time from remote stop signal is deactivated to stop the genset P06 Start Attempts 1 10 times 3 It is maximum of start attempts when starter failed to start...

Page 12: ...0 r min 840 In starting process if genset rotate speed exceed this value it is regarded as genset start success starter will separate P23 Disc Freq 10 30 Hz 14 In starting process if genset frequency...

Page 13: ...stop electromagnet Close before stoping idle ended Open when ETS Delay ended 5 Air Flap Choke Used for genset with choke valve electromagnet Close when gen start and open when safety running delay is...

Page 14: ...or 3s to exit parameter setting status 8 2 RESTORE FACTORY SETTINGS In emergency stop input status press and for 5s at the same time it can restore to default and reset will be displayed on LED 8 3 EL...

Page 15: ...start battery is strictly prohibit 2 Speed Sensor Input NOTE Speed sensor is magnetic equipment which is installed on engine body for testing flywheel teeth number 2 core shielding wire is used for t...

Page 16: ...Table 10 Fault Finding Symptoms Possible Solutions Controller no response with power Check starting batteries Check controller connection wirings Check DC fuse Crank not disconnect Check fuel oil circ...

Reviews: