MGC100 Petrol Genset Controller User Manual                                                                  Page 14 of 16 

8

 

PARAMETERS SETTING 

8.1

 

PARAMETERS REGULATION 

When the controller is running, press

  for 3s, it will enter into 

parameter number menu

 and LED 

will display 

1)

 

Press 

  and 

  to downturn/upturn parameter number; 

2)

 

After parameter number is selected, press 

  to enter into parameter setting menu; press 

  and 

  to increase/decrease parameter value (it can be double-clicked); 

3)

 

Press 

  to confirm modification and save value; 

4)

 

For multiple parameters, step (1-3) can be repeat done for setting; 

5)

 

After parameter setting, press 

  for 3s to exit parameter setting status. 

8.2

 

RESTORE FACTORY SETTINGS 

In  emergency  stop  input  status,  press 

  and 

  for  5s  at  the  same  time,  it  can  restore  to 

default and “reset” will be displayed on LED. 

8.3

 

ELIMINATE ACCUMULATED TIME 

Press 

  and 

  for 5s at the same time, accumulated running time will be reset an “hclr” will 

be displayed on LED. 

NOTE:

 

——

Over voltage threshold must be greater than under voltage threshold. 

——

When  start successfully,  generator  frequency  need  to  be  set  lower  as soon as  possible  in  order  to  starter 

separate sooner. 

——

Number of setting contents refers to “Parameter Content and Range (Table 7)”.   

——

Only  in  parameter  number  menu  can  exit  from  parameter  setting  status.  If  there  is  no  press  operation  in 

parameter number menu, it will exit in 30s automatically. 

 
 
 
 
 
 
 
 

Summary of Contents for MGC100

Page 1: ...MGC100 PETROL GENSET CONTROLLER USER MANUAL...

Page 2: ...NEL 7 4 2 2 ALARM ICON INDICATION 8 4 2 3 PANEL INDICATOR 8 4 3 OPERATION 8 4 3 1 REMOTE START SEQUENCE 8 4 3 2 REMOTE STOP SEQUENCE 8 4 3 3 MANUAL START STOP 9 5 PROTECTION 9 6 CONNECTION 10 7 DEFINI...

Page 3: ...n permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above Any reference to trademarked product names used within this publication is owned...

Page 4: ...lights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictly observed could result in damage or destruction of equipment WARNING Ind...

Page 5: ...atus Chose to control Petrol Genset or Diesel Genset via connection Suitable for 3 phase 4 wire 3 phase 3 wire 2 phase 3 wire single phase 2 wire 120V 240V systems with frequency 50 60 Hz Protection f...

Page 6: ...AC 360V ph N AC 30V AC 360V ph N AC Frequency 50Hz 60Hz Speed Sensor Voltage 1 0V to 24V effective value Speed Sensor Frequency 10000Hz Max Start Relay 7A DC12V power supply Fuel Relay 7A DC12V power...

Page 7: ...icator are normal In setting menu upturn or decrease parameter value it can be double clicked In setting menu press it for more than 3s to exit this menu Page Confirm Switch display contents of nixie...

Page 8: ...y are disengaged for the pre set rest period Crank Rest Time begins and wait for the next crank attempt after the Crank Rest Time delay start for 3s preheat and ETS start to output after Crank Rest Ti...

Page 9: ...2s 2 High Temperature detect when start Alarm Stop when High Temperature is active and lasts for 2s 3 Over Speed detect when start Alarm Stop after duration exceeds Over Speed Stop Delay 4 Gen Over V...

Page 10: ...enset controller When this terminal connected with nothing it used as petrol genset controller 6 High Temperature 1 0mm2 Ground connected is active B 7 Low Oil Pressure 1 0mm2 Ground connected is acti...

Page 11: ...start the genset P05 Stop Delay 0 3600 s 1 Time from remote stop signal is deactivated to stop the genset P06 Start Attempts 1 10 times 3 It is maximum of start attempts when starter failed to start...

Page 12: ...0 r min 840 In starting process if genset rotate speed exceed this value it is regarded as genset start success starter will separate P23 Disc Freq 10 30 Hz 14 In starting process if genset frequency...

Page 13: ...stop electromagnet Close before stoping idle ended Open when ETS Delay ended 5 Air Flap Choke Used for genset with choke valve electromagnet Close when gen start and open when safety running delay is...

Page 14: ...or 3s to exit parameter setting status 8 2 RESTORE FACTORY SETTINGS In emergency stop input status press and for 5s at the same time it can restore to default and reset will be displayed on LED 8 3 EL...

Page 15: ...start battery is strictly prohibit 2 Speed Sensor Input NOTE Speed sensor is magnetic equipment which is installed on engine body for testing flywheel teeth number 2 core shielding wire is used for t...

Page 16: ...Table 10 Fault Finding Symptoms Possible Solutions Controller no response with power Check starting batteries Check controller connection wirings Check DC fuse Crank not disconnect Check fuel oil circ...

Reviews: