MGC100 Petrol Genset Controller User Manual                                                                  Page 9 of 16 

4.3.3

 

MANUAL START/STOP 

a)

 

Press 

  to start genset. It will detect complete start and accelerate to  high-speed  running 

automatically. With  high  temperature,  low  oil  pressure, over  speed  and volt abnormal during 
genset running, controller can protect it to stop quickly (Please refer to Start Sequence b-g). 

b)

 

Press 

  to stop the running genset (Please refer to Stop Sequence b-f).   

NOTE:

 

a)

 

The genset can be stopped manually in remote start status; at this time, remote input is inhibited and it will be 
active when remote input is closed again. 

b)

 

After  start  conditions  are  satisfied,  accumulative  running  timer  will  be  initiated;  at  the  same  time,  the  last 
blinking decimal of nixie tube indicates that genset works normally. 

5

 

PROTECTION 

1)

 

Low Oil Pressure: detect after Safety On, Alarm Stop when Low Oil Pressure input is active and 
lasts for 2s. 

2)

 

High Temperature: detect when start, Alarm Stop when High Temperature is active and lasts 
for 2s. 

3)

 

Over Speed: detect when start, Alarm Stop after duration exceeds Over Speed Stop Delay. 

4)

 

Gen  Over  Volt:  Alarm  Stop  when  the  controller  detects  genset  voltage  exceeds  overvoltage 
value and delay exceeds abnormal delay. 

5)

 

Gen Under Volt: Alarm Stop when the controller detects genset voltage less than under voltage 
value and delay less than abnormal delay. 

6)

 

Emergency  Stop:  ETS  output  immediately  when  Emergency  Stop  is active, in  the  meanwhile 
fuel, preheat and start signal are cut off and Emergency Shutdown Alarm Signal is sent. 

7)

 

Fail to Start: Alarm Stop when start failed in preset start times. 

8)

 

Gen Under Frequency: When genset is normal running, controller detects  gen frequency falls 
below under frequency value and  the  “under  frequency”  delay  has  expired, under frequency 
shutdown alarm will be sent. 

9)

 

Gen  Over  Frequency:  Detection  when  start  genset,  if  gen  frequency  exceeds  over  frequency 
value and the “over frequency” delay has expired, over frequency shutdown alarm will be sent. 

Summary of Contents for MGC100

Page 1: ...MGC100 PETROL GENSET CONTROLLER USER MANUAL...

Page 2: ...NEL 7 4 2 2 ALARM ICON INDICATION 8 4 2 3 PANEL INDICATOR 8 4 3 OPERATION 8 4 3 1 REMOTE START SEQUENCE 8 4 3 2 REMOTE STOP SEQUENCE 8 4 3 3 MANUAL START STOP 9 5 PROTECTION 9 6 CONNECTION 10 7 DEFINI...

Page 3: ...n permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above Any reference to trademarked product names used within this publication is owned...

Page 4: ...lights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictly observed could result in damage or destruction of equipment WARNING Ind...

Page 5: ...atus Chose to control Petrol Genset or Diesel Genset via connection Suitable for 3 phase 4 wire 3 phase 3 wire 2 phase 3 wire single phase 2 wire 120V 240V systems with frequency 50 60 Hz Protection f...

Page 6: ...AC 360V ph N AC 30V AC 360V ph N AC Frequency 50Hz 60Hz Speed Sensor Voltage 1 0V to 24V effective value Speed Sensor Frequency 10000Hz Max Start Relay 7A DC12V power supply Fuel Relay 7A DC12V power...

Page 7: ...icator are normal In setting menu upturn or decrease parameter value it can be double clicked In setting menu press it for more than 3s to exit this menu Page Confirm Switch display contents of nixie...

Page 8: ...y are disengaged for the pre set rest period Crank Rest Time begins and wait for the next crank attempt after the Crank Rest Time delay start for 3s preheat and ETS start to output after Crank Rest Ti...

Page 9: ...2s 2 High Temperature detect when start Alarm Stop when High Temperature is active and lasts for 2s 3 Over Speed detect when start Alarm Stop after duration exceeds Over Speed Stop Delay 4 Gen Over V...

Page 10: ...enset controller When this terminal connected with nothing it used as petrol genset controller 6 High Temperature 1 0mm2 Ground connected is active B 7 Low Oil Pressure 1 0mm2 Ground connected is acti...

Page 11: ...start the genset P05 Stop Delay 0 3600 s 1 Time from remote stop signal is deactivated to stop the genset P06 Start Attempts 1 10 times 3 It is maximum of start attempts when starter failed to start...

Page 12: ...0 r min 840 In starting process if genset rotate speed exceed this value it is regarded as genset start success starter will separate P23 Disc Freq 10 30 Hz 14 In starting process if genset frequency...

Page 13: ...stop electromagnet Close before stoping idle ended Open when ETS Delay ended 5 Air Flap Choke Used for genset with choke valve electromagnet Close when gen start and open when safety running delay is...

Page 14: ...or 3s to exit parameter setting status 8 2 RESTORE FACTORY SETTINGS In emergency stop input status press and for 5s at the same time it can restore to default and reset will be displayed on LED 8 3 EL...

Page 15: ...start battery is strictly prohibit 2 Speed Sensor Input NOTE Speed sensor is magnetic equipment which is installed on engine body for testing flywheel teeth number 2 core shielding wire is used for t...

Page 16: ...Table 10 Fault Finding Symptoms Possible Solutions Controller no response with power Check starting batteries Check controller connection wirings Check DC fuse Crank not disconnect Check fuel oil circ...

Reviews: