HGM9560 BUS TIE MAINS PARALLEL UNIT
HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013-12-30 Version 1.0 Page 37 of 51
19
Reserved
20
Reserved
21
Inhibit Alarm Stop
All shutdown alarms are prohibited except emergence
stop.(Means battle mode)
22
Aux Instrument Mode
All outputs are prohibited in this mode.
23
Reserved
24
Reset Maintenance
Controller will set maintenance time and date as default
when input is active.
25~27
Reserved
28
Remote Start
(On Load)
In
Auto
mode, when the input is active, genset can be
started and with load after genset is OK; when the input
is inactive, genset will stop automatically.
29
Remote Start
(Off Load)
In
Auto
mode, when the input is active, genset can be
started and without load after genset is OK; when the
input is inactive, genset will stop automatically.
30
Aux. Manual Start
In
Auto
mode, when the input is active, genset will start
automatically; when the input is inactive, genset will stop
automatically
31
Remote Start
(On Demand)
In
Auto
mode, when the input is active, all genset that
need to be parallel will start according to the priority and
calling other generator according to the load.
32
Remote Start
(Island)
In
Auto
mode, when the input is active, genset will start
automatically; genset will take load when it is normal
running while mains off load. when the input is inactive,
mains will take load while genset off load and stop
automatically.
33
Simulate Stop key
An external button (not self-locking) can be connected
and pressed as simulate panel.
34
Simulate Manual key
35
Reserved
36
Simulate Auto key
An external button (not self-locking) can be connected
and pressed as simulate panel.
37
Simulate Start key
38
Simulate B-Load key
39
Simulate M-Load key
40~44
Reserved
45
Simulate Mains Normal
In
Auto
mode, when the input is active, mains is normal.
46
Simulate Mains Abnormal
In
Auto
mode, when the input is active, mains is
abnormal.
47
Alternative Config 1
Users can set different parameters to make it easy to
select current configuration via input port.
48
Alternative Config 2
49
Alternative Config 3
50
Reserved