HGM9560 BUS TIE MAINS PARALLEL UNIT 

HGM9560 Bus Tie Mains Parallel Unit        ISSUE 2013-12-30          Version 1.0        Page 30 of 51 

No. 

Items 

Parameters 

Defaults 

Description 

3: Indication 

Active Delay   

(0~20.0)s 

2.0 

Time from detecting active to confirm 

Description   

 

LCD display detailed contents when the 
input is active. 

Flexible Input Port 7 

Contents Setting   

(0~50) 

User defined.    See form 3 

Active Type 

(0~1) 

0: Closed to active     
1: Open to active 

Arming 

(0~2) 

0: From paralleling

 

   

1: Always    2: Never 

Active Actions   

(0~3) 

0: Warn; 1:Trip and stop 2:Trip   
3: Indication 

Active Delay   

(0~20.0)s 

2.0 

Time from detecting active to confirm 

Description   

 

LCD display detailed contents when the 
input is active. 

Flexible Input Port 8 

Contents Setting   

(0~50) 

15 

Mains Closed. See form 3 

Active Type 

(0~1) 

0: Closed to active     
1: Open to active 

Flexible Output Ports 

Flexible Output Port 1 

Contents Setting   

(0~239) 

44 

Bus OK.    See Form 2 

Active Type 

(0~1) 

0:Normally open;       
1:Normally close 

Flexible Output Port 2 

Contents Setting   

(0~239) 

48 

Common Alarm.    See Form 2 

Active Type 

(0~1) 

0:Normally open;       
1:Normally close 

Flexible Output Port 3 

Contents Setting   

(0~239) 

46 

Mains OK. See form 2 

Active Type 

(0~1) 

0:Normally open;       
1:Normally close 

Flexible Output Port 4 

Contents Setting   

(0~239) 

47 

Synchronizing    See form 2 

Active Type 

(0~1) 

0:Normally open;       
1:Normally close 

Flexible Output Port 5 

Contents Setting   

(0~239) 

31 

Close Mains Output. See form 2 

Active Type 

(0~1) 

0:Normally open;       
1:Normally close 

Flexible Output Port 6 

Contents Setting   

(0~239) 

29 

Close Bus Output.    See form 2 

Active Type 

(0~1) 

0:Normally open;       
1:Normally close 

Flexible Output Port 7 

Summary of Contents for HGM9560

Page 1: ...HGM9560 Bus Tie Mains Parallel Unit USER MANUAL Smartgen Technology...

Page 2: ...http www smartgen com cn http www smartgen cn Email sales smartgen cn All rights reserved No part of this publication may be reproduced in any material form including photocopying or storing in any m...

Page 3: ...ication of notation used within this publication SIGN INSTRUCTION NOTE Highlights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not stric...

Page 4: ...TIPLE MAINS OPERATION 19 6 PROTECTIONS 20 6 1 WARNING ALARMS 20 6 2 TRIP AND STOP ALARMS 21 6 3 TRIP ALARM 22 7 WIRING CONNECTION 23 8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS 26 8 1 CONTENTS...

Page 5: ...HGM9560 BUS TIE MAINS PARALLEL UNIT HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 5 of 51 13 TYPICAL APPLICATION 46 14 INSTALLATION 48 15 USB 50 16 FAULT FINDING 51...

Page 6: ...ins Parallel Unit has multiple running states when it is parallel with mains Genset output fixed active power and fixed reactive power Mains peak lopping Provide fixed power to mains Load takeover No...

Page 7: ...ows 3 phase voltage current power parameter and frequency of Bus mains Mains Bus Line voltage Uab Ubc and Uca Line voltage Uab Ubc and Uca Phase voltage Ua Ub and Uc Phase voltage Ua Ub and Uc Phase s...

Page 8: ...tage environment Event log real time clock scheduled start stop generator can be set as start genset once a day week month whether with load or not Accumulative total electric energy A and B Users can...

Page 9: ...upply output Flexible Relay Output 3 7A DC28V power supply output Flexible Relay Output 4 7A AC250V volts free output Flexible Relay Output 5 7A AC250V volts free output Flexible Relay Output 6 7A AC2...

Page 10: ...Slow flashing Slow flashing Trip Alarm Slow flashing Slow flashing Shutdown Alarm Off Fast flashing Trip and Stop Alarm Off Fast flashing Running indicator illuminated from crank disconnect to ETS wh...

Page 11: ...alarm Bus Close Open Can control bus to switch on or off in Manual mode Mains Close Open Can control mains to switch on or off in Manual mode Up Increase 1 Screen scroll 2 Up cursor and increase value...

Page 12: ...egative total active power positive and negative reactive power positive and negative total reactive power positive and negative apparent power total apparent power power factor positive and negative...

Page 13: ...Espanol Clear users accumulation Can clear total electric energy A and B Parameter setting including as following Mains setting Timer settings Battery setting Bus settings Breaker settings Input port...

Page 14: ...nance Synchronization setting Return Mains setting Start Delay Form 3 Use to scroll settings to contirm settings form 4 to return to previous menu form 1 Stop Delay Timers setting Battery setting Bus...

Page 15: ...Bus Tie Mains Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 15 of 51 Start Delay 00008 Form 6 Use to scroll settings to enter settings form 4 to return to previous menu form 1 Stop Delay NOTE Pressi...

Page 16: ...en achieved bus close signal will be initiated and the bus will be paralleled with the mains Once the bus has synchronized to the mains the power will be ramped off the bus 5 If the number of the sync...

Page 17: ...al running press Bus Close Button 1 If mains switch didn t close then bus close relay activate 2 If mains switch already closed the controller will adjust speed and voltage to synchronize bus with mai...

Page 18: ...Manual Stop Operation 1 Stop mode is selected by pressing the button a LED besides the button will illuminate to confirm the operation a If mains switch didn t close then bus open relay activate b If...

Page 19: ...r to the remaining loads If more than one mains supply returns at the same time then the 9560 with the highest priority will take control of the generators and affect a no break changeover back to the...

Page 20: ...troller detects that the Mains Breaker Fail is not configured in the input port it will initiate a warning alarm 5 Digital Input When the digit input port is set as User Configured and the action sele...

Page 21: ...nitiate a trip and stop alarm 5 Mains Under Voltage When the controller detects that the mains voltage has fallen below the pre set value it will initiate a trip and stop alarm 6 Mains ROCOF When the...

Page 22: ...ion signal within the pre set synchronization time it will initiate a trip alarm 3 Bus Breaker Fail When the controller detects that the Bus Breaker Fail is not configured in the input port it will in...

Page 23: ...y If wire length is over 30m better to double wires in parallel Max 20A fuse is recommended 3 COM Output 7 8 2 5mm2 Connected with B 4 Aux output 7 1 5mm2 B is supplied by 3 point rated 16A 5 Aux outp...

Page 24: ...shielding wire is recommended its single end earthed 27 MSC CAN H 0 5mm2 28 MSC CAN L 0 5mm2 33 RS485 Impedance 120 shielding wire is recommended its single end earthed 34 RS485 0 5mm2 35 RS485 0 5mm...

Page 25: ...y coil of current transformer rated 5A 50 Mains CT B phase sensing input 1 5mm2 Externally connected to secondary coil of current transformer rated 5A 51 Mains CT C phase sensing input 1 5mm2 External...

Page 26: ...ay from mains normal to abnormal 6 Volt Trans PT 0 1 0 0 Disable 1 Enable 7 Over Voltage 0 200 120 Setting value is mains rated voltage s percentage and return value default 116 and delay value defaul...

Page 27: ...set 5 Under Frequency 0 200 95 6 ROCOF 0 1 00 Hz s 0 20 Setting value is rate of change of frequency ROCOF action default trip and stop and delay value default 0 1s can be set 7 VECTOR SHIFT 0 20 0 6...

Page 28: ...0 30 s 0 10 Current Transformer 0 1 0 0 Disable 1 Enable 11 CT Ratio 5 12000 5 500 The ratio of external CT 12 Insufficient Capacity Delay 0 1800 s 20 When the controller detects that the bus power pe...

Page 29: ...Open to active 3 Arming 0 2 2 0 From paralleling 1 Always 2 Never 4 Active Actions 0 3 3 0 Warn 1 Trip and stop 2 Trip 3 Indication 5 Active Delay 0 20 0 s 2 0 Time from detecting active to confirm 6...

Page 30: ...nts Setting 0 50 15 Mains Closed See form 3 2 Active Type 0 1 0 0 Closed to active 1 Open to active Flexible Output Ports Flexible Output Port 1 1 Contents Setting 0 239 44 Bus OK See Form 2 2 Active...

Page 31: ...an 0 1Hz then the frequency will be synchronized If the frequency difference is smaller than 0 1Hz then the phase will be synchronized 5 Voltage Difference 0 30 V 3 The voltage difference between bus...

Page 32: ...ust and control before paralleling 19 MSC Number 1 32 2 20 Too Few Modules Action 0 2 1 Action Type 0 No Action 1 Warn 2 Trip 21 Baud Rate 0 3 1 0 500KBit s 1 250KBit s 2 125KBit s 3 50KBit s 22 Sched...

Page 33: ...ion when bus is normal 45 Reserved 46 Mains OK Action when mains is normal 47 Synchronizing Action when controller is synchronizing 48 Common Alarm Action when genset common warning common shutdown co...

Page 34: ...Mains Inactive 126 Mains Over Freq 127 Mains Over Volt 128 Mains Under Freq 129 Mains Under Volt 130 Phase Sequence Wrong 131 Mains Loss of Phase 132 229 Reserved 230 Stop Mode Action in stop mode 23...

Page 35: ...ents of probably condition output S1 output port 1 is active Close when probably condition output S1 is active inactive close when active disconnect when inactive Contents of probably condition output...

Page 36: ...s are illuminating when input is active 6 Panel Lock All buttons in panel is inactive except and there is in the right of first row in LCD when input is active 7 8 Reserved 9 Inhibit Auto Stop In Auto...

Page 37: ...tically 31 Remote Start On Demand In Auto mode when the input is active all genset that need to be parallel will start according to the priority and calling other generator according to the load 32 Re...

Page 38: ...ns may happen NOTE Maximum set value must over minimum set value in case that the condition of too high as well as too low will happen NOTE When setting the warning alarm please set the correct return...

Page 39: ...ch close open test and check if the mains switch is normal then open the mains switch if it is ok 5 Start the HGM9560 controller manually when the bus is normal perform bus switch close open test and...

Page 40: ...BUS TIE MAINS PARALLEL UNIT HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 40 of 51 11 MAINS PARALLEL 11 1 BUS CONTROL MODE Output preset active power reactive power and power...

Page 41: ...bove the power setpoint the generator bus will supply the extra load in order to maintain the mains input at the predefined level mains peak lopping mode If the power value is set as a negative number...

Page 42: ...HGM9560 BUS TIE MAINS PARALLEL UNIT HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 42 of 51 11 3 LOAD TAKEOVER MODE...

Page 43: ...HGM9560 BUS TIE MAINS PARALLEL UNIT HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 43 of 51 11 4 AMF MODE Automatic mains failure mode No break return to mains supply...

Page 44: ...HGM9560 BUS TIE MAINS PARALLEL UNIT HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 44 of 51 11 5 ISLAND MODE...

Page 45: ...HGM9560 BUS TIE MAINS PARALLEL UNIT HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 45 of 51 12 TYPICAL DIAGRAM HGM9560 Typical Diagram...

Page 46: ...ns Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 46 of 51 13 TYPICAL APPLICATION Single Set Communication Note Bus CT is a non issue for single set communication and the bus power can be obtained fr...

Page 47: ...MAINS PARALLEL UNIT HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 47 of 51 MultiSet Communication Note Bus CT is important for multi set communication so make sure that it is s...

Page 48: ...s positive and negative input ports in order to prevent charge disturbing the controller s normal working 2 Output And Expand Relays CAUTION All outputs of controller are relay contact output type If...

Page 49: ...SUE 2013 12 30 Version 1 0 Page 49 of 51 4 Withstand Voltage Test CAUTION When controller had been installed in control panel if need the high voltage test please disconnect controller s all terminal...

Page 50: ...Parallel Unit ISSUE 2013 12 30 Version 1 0 Page 50 of 51 15 USB Users can set the controller s parameters and monitor the controller s status via the test software which provided by Smartgen company...

Page 51: ...own Alarm in running Check related switch and its connections according to the information on LCD Check programmable inputs Genset running while ATS not transfer Check ATS Check the connections betwee...

Reviews: