HGM9560 BUS TIE MAINS PARALLEL UNIT
HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013-12-30 Version 1.0 Page 28 of 51
No.
Items
Parameters
Defaults
Description
over/under voltage. (It is primary
voltage
when
using
voltage
transformer; it is line voltage when AC
system is 3P3W while it is phase
voltage when using other AC system).
3
Rated Frequency
(10.0-600.0)
Hz
50.0
To offer standards for detecting of
over/under frequency.
4
Volt. Trans.(PT)
(0-1)
0
0: Disable; 1:Enable
5
Full Load Active
Power
(1-20000)kW
276
Bu
s’ active power, used for load
distributes.
6
Full Load Reactive
Power
(1-20000)kvar
210
Bus’ reactive power, used for load
distributes.
7
Load Ramp Rate
(0.1-100.0)%
3.0
Speed
rate(%/s)
of
genset
upload/unload
8
Load Ramp Point
(0.1-40.0)%
10.0
Each “Load Ramp Point” unit value
increases, the load will added after
“Load Ramp Delay”.
9
Load Ramp Delay
(0-30)s
0
10
Current
Transformer
(0-1)
0
0: Disable; 1:Enable
11
CT Ratio
(5-12000)/5
500
The ratio of external CT.
12
Insufficient
Capacity Delay
(0-1800)s
20
When the controller detects that the bus
power percentage has exceeded 100%,
after the “Insufficient Capacity Delay”, it
will initiate a corresponding alarm
according to the preset value.
Action: 0: Warn 1: Trip 2: Trip and Stop
13
Insufficient
Capacity Action
(0-2)
0
Switch Setting
1
Close Time
(0~20.0)s
5.0
Pulse width of switch on. When it is 0,
means output constantly.
2
Open Time
(0~20.0)s
3.0
Pulse width of switch off.
Module Setting
1
Power On Mode
(0~2)
0
0:
Stop mode
1:
Manual mode
2:
Auto mode
2
Module Address
(1~254)
1
Controller’s address during remote
sensing.
3
Stop Bit
(0~1)
0
0: 2 stop bits; 1: 1 stop bit
4
Language
(0~2)
0
0: Simplified Chinese 1: English
2: Others
5
Password
(0~65535)
00318
For entering advanced parameters
setting.
Scheduling And Maintenance Setting
1
Scheduled Run
(0~1)
0
0: Disable; 1: Enable
2
Scheduled
Not
Run
(0~1)
0
0: Disable; 1: Enable
3
Maintenance
(0~1)
0
0: Disable; 1: Enable