HGM9560 BUS TIE MAINS PARALLEL UNIT
HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013-12-30 Version 1.0 Page 32 of 51
No.
Items
Parameters
Defaults
Description
Action Type:
0
:
Warn
;
1
:
Trip.
11
Sync Gain
(0-500)
20
Adjust and control before paralleling.
12
Sync Stability
(0-2000)
20
Adjust and control before paralleling.
13
kW Control Gain
(0-500)
20
Adjust and control before paralleling.
14
kW
Control
Stability
(0-2000)
20
Adjust and control before paralleling.
15
Sync Volt Gain
(0-500)
20
Adjust and control after paralleling.
16
Sync Volt Stability
(0-2000)
20
Adjust and control after paralleling.
17
kvar Control Gain
(0-500)
20
Adjust and control before paralleling.
18
kvar
Control
Stability
(0-2000)
20
Adjust and control before paralleling.
19
MSC Number
(1-32)
2
20
Too Few Modules
Action
(0-2)
1
Action Type:
0
:
No Action
;
1
:
Warn
;
2
:
Trip.
21
Baud Rate
(0-3)
1
0
:
500KBit/s
;
1
:
250KBit/s
;
2
:
125KBit/s
;
3
:
50KBit/s.
22
Scheduled
Run
PCT
(0-100)%
80
Schedule the load value of other genset
when start on demand.
23
Scheduled
Stop
PCT
(0-100)%
50
Schedule the load value of other genset
when start on demand.
24
Load Mode Control (0-2)
0
0
:
Bus Control
;
1
:
Mains Control
;
2
:
Load Control.
25
Output
Active
Power
(0-100.0)%
30.0
Used for load control.
26
Reactive
Power
Control
(0-1)
0
0
:
kvar
;
1
:
PF
27
Reactive
Power
Control Value
(0-100.0)%
8.0
Used for load control.
28
Min Start Sets
(1-32)
1
29
Not Reached Act
(0-2)
1
When the controller does not detect the
Min Start Sets during the preset delay,
it will send corresponding alarm signal
according to the action type.
Action Type:
0
:
No Action; 1
:
Warn; 2
:
Trip.
30
Request
Start
Delay
(0-3600)s
120