HAT880 SERIES DUAL POWER BYPASS CONTROLLER USER MANUAL
HAT880 Series Dual Power Bypass Controller 2019-07-11 Version1.1 Page 24 of 49
No.
Paramter Name
Range
Default
Description
4
Schdule Monthly
Optional month
January February March
April May June
July August September
October November
December
Day(1~31)
1
Date for genset start in every month.
5
Schedule Weekly
Optional week
Sunday Monday
Tuesday
Wednesday Thursday
Friday
Saturday
6
Schdule Hours
(0~23)h
0
Scheduled time for starting genset.
7
Schdule Minutes
(0~59)min
0
8
Schdule Work Time
(0~30000)min
30
Lasting time for scheduled running.
9
Gen Inhibit Work Set (0~1)
0
0: Disable 1: Enable
10 Inhibit Period
(0~2)
0
0: Monthly
1: Weekly
2: Daily
11 Inhibit Monthly
Optional month
January February March
April May June
July August September
October November
December
Day(1~31)
1
Date for not starting genset in each month
12 Inhibit Weekly
Optional week
Sunday Monday
Tuesday
Wednesday Thursday
Friday
Saturday
13 Inhibit Hours
(0~23)h
0
Date of not starting the genset
14 Inhibit Minutes
(0~59)min
0
15 Inhibit Rest Time
(0~30000)s
30
Lasting time of not startting the genset
Load
1
Elevator Enable
(0~1)
0
0: Disable ; 1: Enable
2
Elevator Delay
(0~300)s
300
Delay time before load is power off and
switch transfer, which is used to control
the running elevator stops at the nearest
floor until switch transfer is over.
3
Current CT Enable
(0~1)
1
0: Disable ; 1: Enable
4
CT Primary
(5~6000)A
500
CT primary current
5
S1 Full Load Rating
(5~6000)A
500
Full load current of S1 taking load
6
S1 Full Load Rating
(5~6000)A
500
Full load current of S2 taking load
7
S1 Max kW Rating
(1~20000)kW
200
The maximum active power of S1 taking
load
8
S2 Max kW Rating
(1~20000)kW
200
The maximum active power of S2 taking
load
9
Over Current Enable
(0~1)
1
0: Disable ; 1: Enable