HAT880 SERIES DUAL POWER BYPASS CONTROLLER USER MANUAL
HAT880 Series Dual Power Bypass Controller 2019-07-11 Version1.1 Page 20 of 49
9
PARAMETERS CONFIGURATION
9.1
ILLUSTRATION
In the main interface, press
key to enter menu interface; choose
Configuration
and press
again to enter into password confirmation interface. If password is correct, enter into parameter
setting interface, otherwise, exit to main interface directly. Factory default password is
01234
. In
parameter configuration interface, press
key to return to the prior menu.
9.2
PARAMETER CONFIGURATION TABLE
Table 16 - Parameter Configuration Form
No.
Paramter Name
Range
Default
Description
AC Setting
1
S1 Volt Normal
(0~3600) s
10
The delay from S1 voltage abnormal to
normal.
2
S1 Volt Abnormal
(0~3600)s
5
The delay from S1 voltage normal to
abnormal.
3
S2 Volt Normal
(0~3600)s
10
The delay from S2 voltage abnormal to
normal.
4
S2 Volt Abnormal
(0~3600)s
5
The delay from S2 voltage normal to
abnormal.
5
Master Set
(0~1)
0
0: S1 Master
1: S2 Master
6
System Type
(0~3)
0
0: S1M S2G
1: S1G S2M
2: S1M S2M
3: S1G S2G
7
AC System
(0~3)
0
0: 3 Phase,4 Wire (3P4W)
1: 3 Phase,3 Wire (3P3W)
2: 2 Phase,3 Wire (2P3W)
3: Single Phase,2 Wire (1P2W)
8
PT Fitted
(0~1)
0
0: Disable; 1: Enable
9
PT Primary
(30~30000)V
100
Primary voltage of potential transformer
10 PT Secondary
(30~1000)V
100
Secondary voltage of potential transformer
11 Rated Voltage
(0~30000)V
220
Rated voltage of AC system
12 Over Volt Warn
(0~1)
1
0: Disable ; 1: Enable
13 Set Value
(0~200)%
120
Upper limit value of voltage; it is abnormal
if the value has exceeded the set value.
14 Return
(0~200)%
115
Upper limit return value of voltage; it is
normal only when the value has fallen
below the set value.
15 Under voltage Warn
(0~1)
1
0: Disable ; 1: Enable