HAT833 Series Three Power ATS Controller User Manual Page 9 of 56
4
SPECIFICATION
Table 3 – Performance Parameters
Items
Contents
Operating Voltage
1.
DC8.0V~35.0V, continuous power supply
2.
AC(90~305)V power supply A1N1/A2N2/A3N3
Power Consumption
<7W (Standby mode:≤2W)
AC Voltage Input
AC system
3P4W (L-L)
(80~530)V
3P3W (L-L)
(80~625)V (Special order required)
1P2W (L-N)
(50~305)V
2P3W (A-B)
(80~530)V
Rated Frequency
50/60Hz
Programmble Output 1~6
Relay Capacity
16A
AC250V Volts free output
Programmble Output 7~12
Relay Capacity
8A
AC250V Volts free output
Digital Input
GND (B-) connect is active.
Communication
1.
Dual-RS485 isolated interface, MODBUS Protocol
2.
D-type USB port
Case Dimensions
260mmx180mmx54mm
Panel Cutout
242mmx161mm
Working Temperature
(-25~+70)°C
Working Humidity
(20~93)%RH
Storage Temperature
(-25~+70)°C
Protection Level
IP65: when water proof gasket ring inserted between panel and housing.
Insulation Strength
Apply AC1.5kV voltage between high voltage terminal and low voltage
terminal;
The leakage current is not more than 3mA within 1min.
Weight