HAT833 Series Three Power ATS Controller User Manual Page 45 of 56
Maximum pieces of black box record are 5. Every event records total 60s (before and after) data
information of this event, and record once per second. The latest record will cover the oldest one
when records amount exceeds 5. The first record is latest. Users could check details by pressing
Confirm Key, and could check the 60 datas by dredge up/down.
Event log type: the action event of close/open switching in auto mode.
Table 22 – Action Events List
No.
Action Events
Description
1
Auto Action OOO
Open in auto mode
2
Auto Action IOO
QS1 Close in auto mode
3
Auto Action OIO
QS2 Close in auto mode
4
Auto Action OOI
QS3 Close in auto mode
12
SWITCH OPERATION
12.1
MANUAL OPERATION
Manual mode is selected by pressing the
button; a LED besides the button will illuminate
to confirm the operation.
ATS will shart to switch immediately after pressing Switch Key. During the switching,
corresponding lamps will flash, and then the lamp will be normally illuminated when switch is done. If
fail to close or fail to open occurs in the switching process, the controller will alarm (Switch Key is still
active and the operation can be redone).
Table 23 – Manual Transfer Keys
Icon
Key Name
Description
IOO
After pressing this key, if load is off, QS1 will close, otherwise the ATS
open firstly then QS1 will close (S1 supply).
OIO
After pressing this key, if load is off, QS2 will close, otherwise the ATS
open firstly then QS2 will close (S2 supply).
OOI
After pressing this key, if load is off, QS3 will close, otherwise the ATS
open firstly then QS3 will close (S3 supply).
OOO
Load is off after pressing this key.