HAT833 Series Three Power ATS Controller User Manual Page 37 of 56
No.
Item
Description
24
Sync. Switching Inhibit The sync. swithing function is inactive. (HAT833S)
25
Schedule Inhibit
Schedule Start and Schedule Not Start function are deactivated.
26
Simulate S1 OK
Simulate S1 voltage is normal; the S1 voltage abnormal delay is
deactivated.
27
Simulate S2 OK
Simulate S2 voltage is normal; the S2 voltage abnormal delay is
deactivated.
28
Simulate S3 OK
Simulate S3 voltage is normal; the S3 voltage abnormal delay is
deactivated.
29
QS3 Breaker PF Input
When the S3 PF input is active, S3 close relay will activated.
30
S3 Close Inhibit
S3 load is inhibit
31
Gen3 Fault Input
In Cycle start, if the input is active, S3 Gens start will be inhibited.
32
Local Mode
Set controller to local mode.
33
Auto Transfer/Restore
Auto transfer/restore when the input active, auto transfer/nonrestore
when invalid.
34
S3 Master Input
S3 has the highest priority.
35
Non-parallel
Set controller to non-parallel mode.
36
Manual Parallel
Parallel is executed as controller in manual close.
37
Simulate KEY OOO
Same function with Panel OOO Key. Please use reset key to control
ATS to transfer to OOO.
38
Simulate KEY OOI
Same function with Panel OOI Key. Please use reset key to control
ATS to transfer to OOI.
39
Simulate KEY IOO
Same function with Panel IOO Key. Please use reset key to control
ATS to transfer to IOO.
40
Switch 1 Trip
Switch 1 trip fault input is active.
41
Switch 2 Trip
Switch 2 trip fault input is active.
42
Switch 3 Trip
Switch 3 trip fault input is active.
43
Simulate KEY OIO
Same function with Panel OIO Key. Please use reset key to control
ATS to transfer to OIO.
44
Reserved
45
Remote Control Inhibit Remote control is invalid when the input is active.
46
Auto Parallel
Parallel is executed as controller in auto close.
47
Manual/Auto Parallel
Parallel is executed as controller in manual/auto close.
9.3.2
OUTPUT PORTS FUNCTION
Table 20 – Output Ports Function Description
No.
Items
Description
0
Not Used
Invalid
1
Custom Combined 1
2
Custom Combined 2
3
Custom Combined 3
4
Custom Combined 4
5
Custom Combined 5
6
Custom Combined 6